Start-Up Procedure: Apply power to the system
Verify bypass operation
1.Command the UPS into static bypass operation through the UPS display interface:
a.Press the ESC key to open the
b.Select Control on the
c.Select UPS Into Bypass on the Control menu, and press the ENTER key.
d.On the next screen: select Yes, UPS into Bypass, and press the ENTER key.
The BYPASS LED illuminates and the following screens appear:
|
|
|
|
|
| Control | Logging |
|
| ||
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirmation Screen
Confirm
Yes, UPS into Bypass No, Abort
UPS has been
commanded to go into Bypass...
UPS load is in Bypass
Press any key...
Note: The H3 LED above the Q3 circuit breaker illuminates, but do not operate the circuit breaker.
2.Use a true RMS voltmeter to make sure that there is no difference in potential between L1 IN and L1 OUT, L2 IN and L2 OUT, and L3 IN and L3 OUT on the Q3 circuit breaker. The Q3 circuit breaker must be in the OFF position. The top side of Q3 will be utility voltage and the bottom side of Q3 will be the voltage from the UPS in static bypass. Voltage should be less than 2 volts.
Note: Q3 is a
36 | InfraStruXure System - Installation and |