Start-Up Procedure: Apply power to the system
3. Close (turn ON) the Q3 circuit breaker on the InfraStruXure PDU.
Note: The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate the Q2 circuit breaker.
4. Open (turn OFF) the Q2 circuit breaker on the InfraStruXure PDU.
The UPS will display a Forced Bypass message on the display interface and the Fault LED will be red.
5.Command the UPS into static bypass operation through the UPS display interface:
a.Press the ESC key to open the
b.Select Control on the
c.Select UPS Into Bypass on the Control menu, and press the ENTER key.
d.On the next screen: select Yes, UPS into Bypass, and press the ENTER key.
|
|
|
|
|
| Control | Logging |
|
| Status | Display |
|
| Setup | Diags |
|
| Accessories | Help |
|
|
|
|
Control Menu
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirmation Screen
Confirm
Yes, UPS into Bypass No, Abort
Note: The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate the Q2 circuit breaker.
InfraStruXure System - Installation and | 37 |