Installation 2
Series N6700 User’s Guide 27

Multiple Loads

If you are using local sensing and are connecting mu ltiple loads to
one output, connect each load to the output termi nals using separate
connecting wires as shown in the following figure.
This minimizes mutual coupling effects and takes full advantage of
the power system's low output impedance. Keep each pair of wires as
short as possible and twist or bundle them to re duce lead inductance
and noise pickup.
If load considerations require the use of distribution termi nals that
are located away from the instrument, connect the output terminals
to the remote distribution terminals by a pai r of twisted or bundled
wires. Connect each load to the distribution terminals separately.
Remote voltage sensing is recommended under these circumstances.
Sense either at the remote distribution terminal s or, if one load is
more sensitive than the others, directly at the critical load.

Response Time with an External Capacitor

When programming with an external capacitor, vo ltage response time
may be longer than that specified in Appendix A. Use the following
formula to estimate the additional response time for up
programming:
Response Time = (Added Output Capacitor)X(Change in Vout)
Current Limit Setting
Note that programming into an external outpu t capacitor may cause
the power system to briefly enter constant curren t or constant power
operating mode, which adds additional time to t he estimation.

Positive and Negative Voltages

Either positive or negative voltages can be obtained fr om the output
by grounding (or "commoning") one of the output terminals. Always
use two wires to connect the load to the output regardless of where
or how the system is grounded. The instrument can be operated with
any output terminal ± 240 VDC including output voltage from ground.
+S + -S
LOAD
TWIST LEADS
LOAD

+ +

SENSE JUMPERS
INSTALLED FOR
LOCAL SENSING
+
LOAD

+

TWIST
LEADS
LOAD

+

50 A
CONNECTOR
12A & 20 A
CONNECTOR
+S +LS -LS -S
SENSE JUMPERS
INSTALLED FOR
LOCAL SENSING
50A SENSE