Installation

Connections between ACPZ boards (frequency converters or parallel UPSs with SSC)

these connections are made through the special cables supplied;

these connections only concern installations with a Static Switch Cubicle and should be made in addition to the connections between rectifier-inverter cubicles described previously;

the ribbon cable from connector XM133 of the ACPZ board of one rectifier-inverter cubicle is connected to one of the connectors XM127 to XM132 of the ACPZ board of the Static Switch Cubicle.

Important:

Outside the cubicles, group the APOZ inter-board and ACPZ inter-board connections with the inter-cubicle auxiliary connections, and separate this assembly from the power cables.

Connections between each rectifier-inverter cubicle and the Static Switch Cubicle (example of 3 parallel UPS rectifier-inverters with SSC)

ACPZ board

 

 

rectifier-inverter 3

 

 

 

ribbon cable

 

 

supplied

 

XM133

 

 

ACPZ board

 

 

rectifier-inverter 2

 

 

 

ribbon cable

 

 

supplied

 

XM133

 

 

 

ACPZ board

ACPZ board

of the static

rectifier-inverter 1

switch cubicle

 

ribbon cable

 

 

supplied

 

XM133

XM XM XM XM

XM XM

 

127 128 129 130

131 132

Fig. 18

34006451EN/AC - Page 24

Page 24
Image 24
APC 9000 installation manual Xm Xm Xm Xm