2.12 Connection of the battery "Temperature Monitor" (optional)

Connections

This unit must be connected to connector XR4 of the remote relay board of the rectifier-inverter cubicles (see the location of the remote relay board in the figures of the "power circuit connection" section).

use a shielded cable made up of 2 twisted telephone pairs with a conductor cross-section of at least

0.1 mm2 and up to 100 m in length;

do not forget to connect the cable shield to ground pin 7 of connector XR4;

in the case of a parallel UPS configuration, the connections between cubicles may be made by means of a shielded cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables should not exceed 100 m;

a "Temperature Monitor" can only be connected to several rectifier-inverter cubicles when the batteries of these cubicles are located in the same room at the same ambient temperature.

Connection of the battery "Temperature Monitor" (for a single-unit UPS)

battery "Temperature Monitor"

BC+

XR2

XR1

12

(unit shown open)

BC–

+12

shielded cable (2 twisted telephone pairs)

remote relay board connector XR4:

1

 

 

 

2

 

 

 

3

BC

temperature

4

BC +

signal

5

12V

power supply

6

+12V

 

7

 

 

earth

 

 

8

 

 

 

9earth

10

11

12

Fig. 23