34006451EN/AC - Page 5
Characteristics
1.2 Rectifier-inverter cubicle

Characteristics of rectifier-inverter cubicles

1.3 Static Switch Cubicle

Characteristics of Static Switch Cubicles

The parameters given in the table opposite can be used to determine the required rating of a single-unit or modular UPS, a
frequency converter, or a parallel UPS with SSC.
rated
inverter
output
in kVA
cubicle
width W
in mm (1)
cubicle
height H
in mm
cubicle
depth D
in mm
maximum
weight
in kg
heat losses (2)
in kW in cal./s
800 3600 ±10 2000 840 4260 47 11233
900 3600 ±10 2000 840 4260 47 11233
(1) the width of the vertical side clearance bars (25 mm) on each side must be added to the indicated cubicle width, i.e. 50 mm in
all per cubicle. This applies to all cubicle installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load and with the battery float charging. They must be
taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.
The air enters via the doors and grids at the bottom and is discharged via the roof.
rated
SSC
output
in kVA
cubicle
width W
in mm (1)
cubicle
height H
in mm
cubicle
depth D
in mm
maximum
weight
in kg
heat losses (2)
in kW in cal./s
2000 2450 ±10 1900 ±10 840 1710 < 0.5 < 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle
installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load when operating on Mains 2. They are not to be taken
into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.