7 PRINCIPAL DATA

7.1 Electric cable size for SF1-8

Frequency

Voltage

SF1

SF2

SF2

SF4

SF6

SF8

 

 

single-

single-

3-phase

3-phase

3-phase

3-phase

 

 

phase

phase

 

 

 

 

 

 

 

 

 

 

 

 

IEC

 

 

 

 

 

 

 

50 Hz

230 V

2.5 mm²

2.5 mm²

2.5 mm²

2.5 mm²

2x 2.5

2x 2.5

 

 

 

 

 

 

mm²

mm²

50 Hz

400 V

 

 

2.5 mm²

2.5 mm²

2x 2.5

2x 2.5

 

 

 

 

 

 

mm²

mm²

60 Hz

380 V

 

 

2.5 mm²

2.5 mm²

2x 2.5

2x 2.5

 

 

 

 

 

 

mm²

mm²

50 Hz

500 V

 

 

2.5 mm²

2.5 mm²

2x 2.5

2x 2.5

 

 

 

 

 

 

mm²

mm²

 

 

 

 

 

 

 

 

CSA/UL

 

 

 

 

 

 

 

60 Hz

200/230 V

AWG 12

AWG 12

AWG 12

AWG 10

2x AWG

2x AWG

 

 

 

 

 

 

12

10

60 Hz

440/460 V

 

 

AWG 12

AWG 12

2x AWG

2x AWG

 

 

 

 

 

 

12

12

7.2 Electric cable size for SF 6-15 Multi

Frequency

Voltage

SF6

SF8

SF11

SF15

 

 

3-phase

3-phase

3-phase

3-phase

 

 

 

 

 

 

IEC

 

 

 

 

 

50 Hz

230 V

6 mm²

10 mm²

16 mm²

25 mm²

50 Hz

400 V

4 mm²

6 mm²

10 mm²

10 mm²

60 Hz

380 V

4 mm²

6 mm²

10 mm²

10 mm²

50 Hz

500 V

2.5 mm²

4 mm²

6 mm²

10 mm²

 

 

 

 

 

 

CSA/UL

 

 

 

 

 

60 Hz

200/230 V

AWG 8

AWG 6

AWG 4

AWG 3

60 Hz

440/460 V

AWG 10

AWG 10

AWG 8

AWG 6

60 Hz

575 V

AWG 12

AWG 10

AWG 8

AWG 6