Instruction book
8.15 Programmable settings
8.15.1 Regulation settings
| 
 | 
 | Minimum | Nominal | Maximum | |
| 
 | 
 | setting | setting | setting | |
| 
 | 
 | 
 | 
 | 
 | |
| Number of motor starts | starts/day | 240 | 720 | 720 | |
| Minimum stop time 1) | sec | 5 | 5 | 30 | |
| Stop between 2 compressor | sec | 2 | 2 | 5 | |
| modules | |||||
| 
 | 
 | 
 | 
 | ||
| Start between 2 compressor | sec | 2 | 2 | 10 | |
| modules | |||||
| 
 | 
 | 
 | 
 | ||
| Power recovery time 3) | sec | 10 | 10 | 3600 | |
| Delay at restarting after | sec | 0 | 0 | 1200 | |
| power recovery 3) | |||||
| 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | 
 | 
 | |
| Minimum pressure 2) | 
 | 
 | 
 | 
 | |
| 8 bar Pack | bar(e) | 4 | 7 | 7.9 | |
| 8 bar  | bar(e) | 4 | 6.8 | 7.7 | |
| 10 bar Pack | bar(e) | 4 | 9 | 9.9 | |
| 10 bar  | bar(e) | 4 | 8.8 | 9.7 | |
| 100 psi Pack | bar(e) | 4 | 7 | 7.9 | |
| 100 psi  | bar(e) | 4 | 6.8 | 7.7 | |
| 125 psi Pack | bar(e) | 4 | 8.1 | 9 | |
| 125 psi  | bar(e) | 4 | 7.75 | 8.8 | |
| 145 psi Pack | bar(e) | 4 | 9 | 9.9 | |
| 145 psi  | bar(e) | 4 | 8.8 | 9.7 | |
| 
 | 
 | 
 | 
 | 
 | |
| Maximum pressure 2) | 
 | 
 | 
 | 
 | |
| 8 bar Pack | bar(e) | 4.1 | 8 | 8 | |
| 8 bar  | bar(e) | 4.1 | 7.8 | 7.8 | |
| 10 bar Pack | bar(e) | 4.1 | 10 | 10 | |
| 10 bar  | bar(e) | 4.1 | 9.8 | 9.8 | |
| 100 psi Pack | bar(e) | 4.1 | 8 | 8 | |
| 100 psi  | bar(e) | 4.1 | 7.8 | 7.8 | |
| 125 psi Pack | bar(e) | 4.1 | 9.1 | 9.1 | |
| 125 psi  | bar(e) | 4.1 | 8.9 | 8.9 | |
| 145 psi Pack | bar(e) | 4.1 | 10 | 10 | |
| 145 psi  | bar(e) | 4.1 | 9.8 | 9.8 | |
| 
 | 
 | 
 | 
 | 
 | |
| For  | 
 | 
 | 
 | 
 | |
| Dewpoint warning | °C | 3 | 15 | 40 | |
| temperature | |||||
| 
 | 
 | 
 | 
 | ||
| Delay at signal 5) | sec | 0 | 3 | 10 | |
| Delay at starting 6) | sec | 0 | 255 | 255 | 
| 2920 1521 00 | 64 | 