Instruction book
1.7 Air dryer on SF Full-Feature (Fig. 1.15)
Compressed air circuit
Wet compressed air enters heat exchanger (13) and is cooled by the outgoing, cold, dried air. Water in the incoming air starts to condense. The air then flows through heat exchanger (11) where the refrigerant evaporates and withdraws heat from the air. More water in the air condenses. The cold air then flows through condensate separator (3) where the condensate is separated from the air. The condensate is automatically drained through outlet (5). The cold, dried air then flows through heat exchanger (13), where it is warmed up by the incoming air.
Refrigerant circuit
Compressor (M1) delivers hot,
The liquid flows through liquid refrigerant dryer/filter (12) to capillary tube (7). The refrigerant leaves the capillary tube at evaporating pressure.
The refrigerant enters evaporator (11) where it withdraws heat from the compressed air by further evaporation at constant pressure. The heated refrigerant leaves the evaporator and is sucked in by the compressor.
| AIR (1) |
| REFRIGERANT GAS (2) |
| REFRIGERANT LIQUID (3) |
2 | 1 |
AO |
|
AI
13 |
|
|
| Text on Fig. 1.15 | |
11 |
|
|
| 3 |
|
|
|
|
| (1) | Air |
|
|
| 4 | (2) | Refrigerant gas |
|
|
| 6 | (3) | Refrigerant liquid |
|
|
|
|
| |
| 10 | 7 | 5 |
|
|
| 12 |
|
|
|
|
| S3 |
|
|
|
|
| 9 |
|
|
|
|
| M1 |
|
|
|
|
| 8 |
|
|
|
|
| M2 |
|
|
|
|
| 50972D |
|
|
|
|
AI | Wet air inlet |
| 5 | Automatic condensate drain | |
AO | Dry air outlet |
| 6 | Manual condensate drain valve | |
M1 | Refrigerant compressor |
| 7 | Capillary tube |
|
M2 | Condenser fan motor |
| 8 | Condenser cooling fan |
|
S3 | Fan control switch |
| 9 | Refrigerant condenser |
|
1 | Pressure dewpoint sensor |
| 10 | Hot gas |
|
2 | Insulating block |
| 11 | Air/refrigerant heat exchanger/evaporator | |
3 | Condensate separator |
| 12 | Liquid refrigerant dryer/filter | |
4 | Condensate trap |
| 13 | Air/air heat exchanger |
|
Fig. 1.15 Dryer on SF Full-Feature
2920 1521 00 | 16 |