Instruction book
8.7 Modify parameters menu
Function
The menu allows the operator to program:
-Parameters, see section 8.8.
-Protections settings, see section 8.9.
-Service plan settings, see section 8.10.
-Clock function settings, see section 8.11.
-Configuration settings, see section 8.12.
8.8 Modifying parameters
Function
To modify a number of parameters as mentioned below and in Fig. 8.1.
-Pressure Band 1 High
-Pressure Band 1 Low
-Pressure Band 2 High
-Pressure Band 2 Low
-Number Of Starts/Day (per compressor module)
-Minimum Stop Time (i.e. the time period during which the compressor, if stopped automatically, remains stopped whatever happens with the air net pressure)
-Power recovery time (if automatic restart after voltage failure is activated) 3)
-Restart delay (can be programmed, allowing e.g. compressors to be restarted one after the other)
-Time to next start (time between the starting of two compressor modules)
-Time to next stop (time between the stopping of two compressor modules during regulation)
Procedure
1.Starting from the Main screen (see section 8.1.2):
-press the key "Menu" (F1)
-press the ↓ key until the option "Modify Parameters" is followed by a horizontal arrow
-press the tabulator key (5) to activate the menu
2.The first option ("Parameters") will be followed by a horizontal arrow.
3.Press the tabulator key (5): the first item ("Pressure Band 1 High") and its setting will appear.
4.Use the ↓ key to scroll until the parameter to be modified is followed by a horizontal arrow.
2920 1521 00 | 49 |