Bosch Appliances DS7400XI, DS7445I Typical Burglar And Fire Wiring, Alarm Output, Auxiliary Power

Models: DS7445I DS7447 DS7400XI DS7447E

1 100
Download 100 pages 4.36 Kb
Page 10
Image 10
TYPICAL BURGLAR AND FIRE WIRING
Shared cable is not recommended for keypad, multiplex, options bus, telephone, or siren wiring.

3.0Control Terminal Wiring

 

 

 

 

 

TYPICAL BURGLAR AND FIRE WIRING

Zone

 

Loop +

Zone

 

Loop +

Zone

 

Loop +

Aux. Power (—)

 

 

 

Input

 

 

 

Input

 

 

 

Input

 

or PO2

(terminal 5 or 7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z–

 

L+

 

 

Z–

 

L+

 

 

Z–

 

L+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING

CAUTION

Before servicing, remove all power including the transformer, battery and phone line. A complete functional test is required after any programming.

Incorrect connections may result in damage to the unit.

System is Power Limited except for battery terminals. All wiring entering this enclosure must be power limited.

in +

+

out

Power

 

 

Alarm

 

NO

 

 

NC

 

 

in +

+ out

Power

 

Typical burglar

Typical 2-wire

Alarm

alarm loop wiring

smoke detector

 

 

wiring

 

 

 

A/C Power Indication LED

1

 

EARTH GROUND: Must be connected to

 

a good earth ground such as a cold water

 

 

2

 

pipe and also connected to the cabinet cover,

 

using the supplied wire jumper.

3

A

A/C INPUT: Use U. L. listed, 18 VAC 50

VA, class 2 transformer. Model TR-1850

 

4

C

requires 50/60 Hz. unswitched dedicated

 

outlet - do not share.

5

ALARM OUTPUT:

 

 

Provides 12 VDC, special application, up to

6

A

1.75 A for powering bells, siren drivers, etc.

Function programmed in address 2734.

 

 

7

AUXILIARY POWER:

 

 

Provides 12 VDC, special application, up to

8

+

1.0 A for powering detectors.

 

R

O

OPTION BUS:

B

P

T

Used for options such as the DS7416i

G

I

Communications Module, the DS7420i Dual

O

Phone Line Module, etc.

Y

N

Also for keypads #11 - #15.

 

 

For Commercial Fire Mode: Option Bus wiring

 

 

should be in conduit if run ouside the

 

 

enclosure.

KEYPAD BUS*:

PHONE LINE:

 

Up to 15 keypads**

 

 

 

 

 

may be used. Can be

 

 

 

 

 

“home-run” or

 

 

 

 

 

 

“daisy-chained.”

 

T

TH

RH

R

R

B

G

Y

G

B

S

 

R

 

 

 

 

 

 

 

 

 

9

10

1

12

13

14

15

 

16

 

 

 

 

 

 

 

 

 

(for a list of

 

 

 

 

 

 

 

compatible 2-wire

 

 

 

 

 

 

 

 

End-of-Line

 

 

 

smoke detectors,

 

 

 

Supervision Relay

 

 

 

 

 

(e.g. Detection Systems’

 

 

 

see Technical Service

 

 

 

 

 

 

 

 

 

EOL200)

 

Note P/N 27685)

 

Typical 4-wire smoke

 

 

 

 

 

 

detector wiring.

 

 

 

 

For example:

 

 

Detection Systems’

 

DS250 in an MB4W base.

An appropriate two pole disconnect device must be installed

by qualified service personnel, as part of the building installation.

CAUTION

Danger of explosion if battery is incorrectly replaced.

 

Replace with the same or equivalent type

CAUTION

recommended by the manufacturer.

Dispose of used batteries according to the

 

manufacturer's instructions.

PROGRAMMABLE OUTPUTS:

PO1 shorts to aux. power negative when activated, PO1 can sink up to 1.0 A. PO1 function programmed in address 2735.

PO2 supplies 12 V and up to 500 mA when activated.

PO2 function programmed in address 2736.

ZONES 1-8:Zones 1-8 are intended for connection of Normally Open or Normally Closed alarm contacts. They may also be used for compatible 2-wire smoke detectors. These zones require a 2.21kΩ resistor (P/N 25899) at the end of the loop. Power is momentarily removed from L+ after a [PIN] + [System Reset] or during a fire verification.

Zone 1-8 assignments are programmed in address 0031-0038.

PO1 PO2

1–

L+

2–

3–

L+

4–

5–

L+

6–

7–

L+

8–

17

18

19

20

21

22

23

24

25

26

27

28

29

30

Keypad

(#1 - #10)

Keypad

(#1 - #10)

* = Maximum wire length each: 1000 ft. (305 m).

Maximum wire length total in system: 6000 ft. (1830 m) when using #22 AWG (0.8 mm) or #18 AWG (1.0 mm) cable.

**= Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15 connect to the Option Bus.

NOTE

Page 10 P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide