Bosch Appliances DS7447E •Output Functions, Input/Output Cross Matrixing, •Multiplex Bus Outputs

Models: DS7445I DS7447 DS7400XI DS7447E

1 100
Download 100 pages 4.36 Kb
Page 21
Image 21
•Output Functions

-Smoke alarm. This must be the odd numbered zone of the zone pair required for these devices. The zone must be programmed with a zone function that is set for Fire Zone and Trouble onOpen.

-Low Temperature Alarm. This must be the even numbered zone of the zone pair required for these devices. This zone must be programmed with a zone function that is set as Supervisory and Trouble on Open.

6.4Output Programming

Latch on Any Zone Alarm: This is an output programmed to activate upon any zone alarm (including invisible zones) and will latch until the system has been disarmed.

-If this output is programmed to respond only to a fire zone, it will remain latched until the fire reset command is performed.

ON during Entry Pre-Alert: This is an output programmed to activate when an entry/exit zone is violated while the system is armed.

-It will remain activated until the system is disarmed, or until the entry delay time has expired.

ON for 10 seconds after [PIN] + [System Reset] is entered: This is an output programmed to activate for 10 seconds after the fire reset command is entered at the keypad or if a Fire Zone with Verification activates.

-This output is intended to be used to power 4-wire smoke detectors or any other device that requires a power interruption to reset an alarm condition.

NOTE: When Programmable Output 2 is programmed this way, it will normally supply auxiliary power and will turn OFF for 10 seconds when the fire reset command is entered.

ON when System is Armed: This is an output programmed to activate when the system is armed.

-It will remain activated until the system is disarmed.

Ground Start: This is an output programmed to activate for 3 seconds when the phone line is seized. It is intended for use with ground start phone systems that require a momentary short to ground to obtain a dial tone.

-Connect a separate 12 VDC, DPDT relay.

-Connect both relay contact commons to ground, and connect the Normally Open of each contact to terminal positions 13 and 16 (one to terminal 13, the other to 16) of the DS7400Xi.

-This output follows all partitions regardless of how data digit 2 of the output programming address is programmed.

-Not intended for UL Listed systems. Not for use with phone line monitors.

System Status (ready to arm): This is an output programmed to follow the Status LED of the keypad.

-It will activate when the system is ready to arm with no zones violated.

Zone Alarm: This is an output programmed to activate when a zone is in an alarm condition.

-It will remain activated until the system is disarmed or the bell cut-off time expires.

-This output is intended to activate alarm bells and sirens.

-This will not activate from Silent or Invisible Zones.

Zone Alarm Delayed by 20 sec.: This is an output programmed to wait 20 seconds after a zone enters an alarm condition to activate.

-It will remain activated until the system is disarmed or the bell

cut-off time expires.

-This output is intended to activate alarm bells and sirens, but provides a delay to allow the user to silence the system before it activates.

Output Functions

Output Functions can be programmed to follow system events or to follow one or two specific zones in a “cross-matrix” fashion (see Input/Output Cross-Matrixing).

-These Output Functions can be programmed to control Octal Relay outputs or Multiplex Bus outputs.

-Output Functions are programmed in addresses 2772-2843.

Input/Output Cross Matrixing

Input/Output Cross Matrixing allows Output Functions to follow the status of specific input zones (zones 1 through 248 only).

-Outputs can be programmed to follow any combination of one or two zones, open or closed, with the system armed or dis- armed.

-If programmed to latch, the output will latch until a valid PIN is entered at the keypad.

Keypad Sounder Output: This is an output programmed to follow the keypad sounder.

-It activates during the entry pre-alert and during any day monitor alarm. It does not follow momentary keypad beeps such as keystrokes, chimes, etc.

Access Output: This is an output programmed to activate for 10 seconds when an access control PIN is entered at the keypad.

-Not UL Listed for Access Control (UL294).

Panic/Duress Output: All outputs, including the three on-board outputs, the Octal Relays, and the Output Functions, support a Panic/Duress function. This output will follow Duress activations, Keypad Emergency Keys B and C, and Invisible and Silent Zone alarms. It will only be reset by a user acknowledgement and will not reset after the burglary bell time-out occurs. Duress activa- tions will latch until acknowledged by a user.

Multiplex Bus Outputs

The DS7400Xi supports up to 60 DS7465 Input/Output Modules.

-These modules are connected to the multiplex bus and provide one input loop and one Form “C” output relay.

-The input loop operates the same as all other multiplex inputs.

-The output loop can be programmed to follow Output Functions.

-Multiplex Bus outputs can be bypassed using the bypass function. If an output zone is bypassed while it is ON, it will turn OFF. The bypass will not be removed when the system is armed and then disarmed; it must be cancelled by entering the bypass command again or by cancelling all bypasses.

NOTE: DS7465 Module outputs will not pulse, even if programmed to do so.

Octal Relay Modules (DS7488)

The DS7400Xi can support two Octal Relay Modules.

-Each relay can be programmed to follow system-wide events or Output Functions as described above.

Solid State Output Modules (DS7489)

The DS7400Xi can support two Solid State Output Modules.

-Each output can be programmed to follow system-wide events or Output Functions as described above.

6.5Partition Control Programming

Partition Control Programming: Up to eight partitions may be used. They are assigned (program address 3420) in order.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01 Page 21

Page 21