Bosch Appliances DS7400XI General Information, System Faults, Event History, # 8 7 will display

Models: DS7445I DS7447 DS7400XI DS7447E

1 100
Download 100 pages 4.36 Kb
Page 30
Image 30
7.7.1 General Information

least two seconds. The system will also drop out of Single Par- tition Mode after 40 seconds without a keypad entry.

7.7Keypad Error Displays

7.7.1 General Information

Display

Meaning

DS7445/DS7445i: Power LED flashing

There is an Error Message. To

DS7447/DS7447E: Control Trouble Enter #87

display the message, enter [PIN] + [#]

 

[8] [7].

DS7445/DS7445i: LED 1 On

There is a power failure, and the

DS7447/DS7447E: AC Power Failure

panel is operating on backup battery

 

power.

DS7445/DS7445i: LED 2 On

If the system has just been through a

DS7447/DS7447E: Battery Trouble*

power failure, wait at least two hours

 

for the battery to recharge, the enter

 

[PIN] + [System Reset] to perform a

 

battery test,

DS7445/DS7445i: LED 3 On

The communicator failed to

DS7447/DS7447E: Communicator Err**

communicate with the Central

 

Station.

DS7445/DS7445i: LED 4 On

Internal error in the control circuitry or

DS7447/DS7447E: System Fault

optional circuitry. See System Faults.

DS7445/DS7445i: LED 5 On

One of the keypads is not responding

DS7447/DS7447E: Keypad Fault

to the Control Panel.

DS7445/DS7445i: LED 6 On

One of the keypad housings has

DS7447/DS7447E: Keypad Tamper

been opened.

DS7445/DS7445i: LED 7 On

The multiplex bus is defective or has

DS7447/DS7447E: Multiplex Bus

been shorted.

DS7445/DS7445i: LED 8 On

The auxiliary power has been

DS7447/DS7447E: Aux. Power Fault

shorted.

DS7445/DS7445i: not applicable

One of the zones is not responding to

DS7447/DS7447E: Zone Trouble

the Control Panel. This may also be

 

displayed during power-up; if so,

 

ignore it.

DS7445/DS7445i: not applicable

Indicates a problem with an RF

DS7447/DS7447E: RF

(wireless) zone.

DS7445/DS7445i: not applicable

One of the multiplex smoke detectors

DS7447/DS7447E: Dirty Chamber

has failed the sensitivity test and may

 

require cleaning or replacement. The

 

keypad beep may be cleared by

 

entering [PIN] + [Off].

Error Displays can only be read when the control is disarmed. Some Control Panel Errors, such as battery trouble and any RF troubles, will cause the keypad sounders to beep every 10 seconds. The keypad sounders may be silenced for 4 hours by entering:

[PIN] + [Off].

The sounders will continue to resound until the problem is fixed. To Clear a display, enter:

[PIN] + [System Reset].

Clear the Error Display only on the advice of your installing company or if you are certain the problem has been remedied.

NOTE: System faults may be read from any keypad because they are system-wide. All other Error Displays are limited to the partition the standard keypad is in. If you are on a Master keypad, you may read Error Displays one partition at a time.

7.7.2 System Faults

System faults are designated as follows:

[#] [8] [7] will display

[#] [8] [9] will

 

display

 

 

RAM Fault

System Fault 01

 

 

ROM Fault

System Fault 02

 

 

EEPROM Fault

System Fault 03

 

 

Ground Fault

System Fault 04

 

 

2Ph/Bell Fault = loss of communication to

System Fault 10

DS7420i

 

 

 

Line 1 Fault = DS7420I phone line 1 fault

System Fault 11

 

 

Line 2 Fault = DS7420I phone line 2 fault

System Fault 12

 

 

Bell Fault = DS7420i bell circuit fault

System Fault 13

 

 

Aux. Relay Fault = DS7420I auxiliary relay

System Fault 14

fault

 

 

 

Oct. Relay Fault = loss of communication to

System Fault 20

DS7488

 

 

 

Reserved for older panels

System Fault 50

 

 

AR IB Queue Full = modem buffer full

System Fault 51

 

 

AR Host Down = network data switch down

System Fault 52

 

 

AR Unreg. Modem = modem not registered

System Fault 53

 

 

AR Power Fail = power source below

System Fault 54

defined threshold

 

 

 

AR Network Lost = loss of network

System Fault 55

 

 

AR Modem HW Err = modem hardware

System Fault 56

error

 

 

 

AR Modem SW Err = modem software

System Fault 57

error

 

 

 

AR Opt. Bus Err = loss of communications

System Fault 58

to ARDIS module

 

 

 

AR Corrupt MSG = message error

System Fault 59

 

 

7.7.3 Event History

The History Buffer stores the last 400 events in memory. The DS7447/DS7447E can display all of these events. If this test is performed from a Master keypad, it must be in Single Partition Mode. The DS7445/DS7445i will only display those zones (1-8) that have alarmed since the last Event History Readback. The RF3341 cannot display history events.

To readback the Event History Buffer:

Press [PIN] + [#] [8] [9]. On a DS7447/DS7447E keypad, the last event to take place will be displayed. On a DS7445/DS7445i keypad, the zone LEDs for any zones that have alarmed since the last Event History Readback in that partition will flash.

Scroll through the events using the [9], [6], and [#] keys as follows: To begin scrolling back through the events, press the [#] key. The [#] key will scroll you back through the history line by line. The [9] key will scroll you back in reverse chronological order by event. A [6] will scroll you back up through the events (toward the most recent) by event.

Each event consists of two or three lines or display screens. The first line/screen will be the event title and user. The second line/ screen will be the date of the event or the change being made. If there is a third line/screen, it will be the date of the change.

NOTE: When performing this from a Master keypad, each partition will display its own history.

To exit the Event History Mode, press the [*] key or wait 20 seconds and the keypad will exit automatically.

Page 30 P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Page 30
Image 30
Bosch Appliances DS7400XI, DS7445I manual General Information, System Faults, Event History, # 8 7 will display, # 8 9 will