Central Station Burglary Alarm -

11.4General System Requirements

Applies to the following grades only:

Local Burglary

Grade A using Digital Alarm Communicator

Alarm -

Transmitter (DACT)

Police Station

Grades AA and A using DACT and DS7416i

Connection -

Communications module.

 

Grade A using DACT and local Bell.

Grades AA and A using DACT and DS7416i Communications module.

Grade B using DACT and local bell.

Grade C using Digital Alarm Communicator Transmitter only.

The controls must be installed in accordance with UL Standards UL681 and UL609 for all grades of service.

1. Report Programming:

Burglar Zone Reports must be programmed for those zones used.

Low Battery Report (Program Address 3336) must be programmed.

AC Failure Report (Program Address 3338) must be programmed.

Open Report (Program Address 3331) must be programmed.

Close Report (Program Address 3332) must be programmed.

24-Hour Check-In Reports (Program Addresses 3340 and 3347) must be programmed.

2. General Control Programming:

The control must not be programmed for auto disarm.

Must be programmed for no swinger shunts and closing ringback. (Program Address 0000 data digit 2, enter 0, 1, or 2).

Program Address 2732 must be programmed as: Data Digit 1= 0, Data Digit 2= 0.

3. Zone Function Programming:

The Burglar alarm signal (whether pulsed or steady) must be different from the Fire alarm signal.

4. Alarm Output Programming:

Program Address 2734 must be programmed as: Data Digit 1= 6, Data Digit 2 = 3.

Program Address 2737 must be programmed as: Data Digit 1= 8.

11.4.1Local Burglary Alarm

A.Grade A Installations using Digital Alarm Communicator Transmitter with local bell

Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection System’s model AE3CC enclosure with a cover actuated tamper switch installed.

An Ademco Model AB-12 bell/housing (see section 11.6).

1. Timer Programming:

Bell Cutoff Times (Program Addresses 4032 and 4033) must be programmed for not less than 15 minutes.

Entry, Exit Delay Times (Program Addresses 4028-4029) must be programmed for not longer than 60 seconds.

11.4.2Police Station Connection

Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection Systems’ model AE3CC enclosure with a cover actuated tamper switch installed.

An DS7416i (or DataTAC) interface module.

The DS7416i module and antenna should be mounted within the protected area.

The Detection Systems’ model DS7481 Phone Line Monitor.

1. Timer Programming:

Entry, Exit Delay Times (Program Addresses 4028-4030) must be programmed for not longer than 60 seconds.

B.Grade A Installations Using Digital Alarm Communicator Transmitter With Local Bell

Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection System’s model AE3CC enclosure with a cover actuated tamper switch installed.

The Ademco Model AB-12 bell/housing (see section 11.6).

1. Timer Programming:

Bell Cutoff Times (Program Addresses 4032 and 4033) must be programmed for not less than 15 minutes.

Entry, Exit Delay Times (Program Addresses 4028-4030) must be programmed for not longer than 60 seconds.

11.4.3Central Station Burglary Alarm and Proprietary

A.Central Station Burglary Grades AA and A and Proprietary Grade AA Installations Using an DS7416i Interface Module Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection Systems’ model AE3CC enclosure with a cover actuated tamper switch installed.

An DS7416i (or DataTAC) interface module.

The DS7416i module and antenna should be mounted within the protected area.

The Detection Systems’ model DS7481 Phone Line Monitor.

The Ademco Model AB-12 bell/housing (see section 11.6).

1. Timer Programming:

Entry, Exit Delay Times (Program Addresses 4028-4030) must be programmed for not longer than 60 seconds.

B.Grade B Installations Using Digital Alarm Communicator Transmitter With Local Bell

Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection Systems’ model AE3CC enclosure with a cover actuated tamper switch installed.

The Ademco Model AB-12 bell/housing (see section 11.6).

1. Timer Programming:

Bell Cutoff Times (Program Addresses 4032 and 4033) must be programmed for not less than 15 minutes.

Entry, Exit Delay Times (Program Addresses 4028-4030) must be programmed for not longer than 60 seconds.

C.Central Station Burglary Grade C and Proprietary Grade A Installations Using Digital Alarm Communicator Transmitter only Follow General System Requirements as listed in 11.4.

Required Accessories:

The control must be in the Detection System’s model AE3CC enclosure with a cover actuated tamper switch installed.

1. Timer Programming:

Entry, Exit Delay Times (Program Addresses 4028-4030) must be programmed for not longer than 60 seconds.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01 Page 77

Page 77
Image 77
Bosch Appliances DS7447E, DS7445I General System Requirements, 11.4.1Local Burglary Alarm, 11.4.2Police Station Connection

DS7445I, DS7447, DS7400XI, DS7447E specifications

Bosch Appliances offers a range of state-of-the-art home solutions, with models like the DS7447, DS7400XI, DS7445I, and DS7447E showcasing advanced technology and innovative design. Each of these models reflects Bosch's commitment to quality, efficiency, and user convenience.

The Bosch DS7447 is designed for the modern kitchen. This model features a fully integrated design, allowing it to blend seamlessly into any cabinetry. With a spacious capacity, it accommodates various cooking needs, ensuring every home chef has ample room. Its intuitive control panel simplifies operation, allowing users to select temperature settings with ease. The energy-efficient technology contributes to lower utility bills while still delivering outstanding performance.

Moving on to the Bosch DS7400XI, this model stands out due to its sleek stainless steel finish, which not only enhances its aesthetic appeal but also offers durability. It is equipped with advanced cooling technology that ensures even temperature distribution, extending the lifespan of stored food. This model also incorporates a sophisticated air filtration system, eliminating unwanted odors and maintaining a fresh environment within the appliance. The adjustable shelving adds flexibility to storage options, accommodating items of varying sizes.

The Bosch DS7445I combines style and functionality. This particular model is highlighted by its quiet operation, making it a great choice for open-concept living spaces. With a focus on user-friendliness, it features a digital display and smart sensors that monitor performance and inform users when maintenance is required. Furthermore, this model is known for its eco-friendly operation, utilizing minimal energy without compromising on effectiveness, making it suitable for environmentally conscious households.

Finally, the Bosch DS7447E brings innovation to the forefront with its smart connectivity features. Users can control and monitor the appliance remotely via a smartphone app, allowing for a seamless cooking experience even when away from home. The model also boasts quick-cooling technology, ensuring that items are chilled faster without sacrificing quality. The design emphasis placed on user accessibility strengthens its appeal for diverse households.

In conclusion, Bosch Appliances' DS7447, DS7400XI, DS7445I, and DS7447E each offer unique benefits tailored to meet various needs. With exceptional quality, advanced technologies, and user-centered designs, Bosch continues to position itself as a leader in the home appliance market.