Programming a Zone
Programming a Zone is a four step process. These steps must be performed, in order, to program a zone.
•Step 1 is programming Zone Functions (what the zone will do in alarm),
•Step 2 is assigning a Zone Function to the zone.
•Step 3 is assigning a Zone Type to the zone.
•Step 4 is assigning the zone to a partition.
Step 1: Programming the Zone Functions
10.2Zone Function Programming: Program Addresses
A Zone Function is the description of how a zone will behave. Up to 30 different Zone Functions may | Data Digit | |||||||||||||||||||||||||||||||||
be programmed. You may use the default values (which are already programmed into the panel) and |
|
| 1 |
| 2 |
| ||||||||||||||||||||||||||||
skip this step, or change the defaults, or add new Zone Functions. See section 6.2 for further |
|
|
|
|
|
|
| |||||||||||||||||||||||||||
details. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
| Enter the Data Digit as a: |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
| Select Options | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | *2 | *3 | *4 | *5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
| Invisible Alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Select Option |
|
|
| DD |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
| Silent Alarm |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Interior Delayed |
|
|
| 0 |
|
| ||||||||
|
| Steady Alarm Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Perimeter Instant |
|
|
| 1 |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| Pulsing Alarm Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 |
|
| |||||||||||
|
| Alarm on Short |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Entry/Exit Delay #1 |
|
|
| 3 |
|
| |||||||
|
| Alarm on Open |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
| Trouble on Open** |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Entry/Exit Delay #2 |
|
|
| 4 |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Trouble on Short |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Interior Entry/Exit Follower |
| 5 |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| *2 - *5 are Hex values. They will display as C - F at the keypads. |
|
| Interior Home/Away |
|
|
| 6 |
|
| ||||||||||||||||||||
|
|
| ** = Only when disarmed. When armed, this becomes Alarm on Open or Short for |
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||
| Interior Instant |
|
|
| 7 |
|
| |||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||
| Day Monitor |
|
|
| 8 |
|
| |||||||||||||||||||||||||||
|
|
|
| not be programmed for Trouble on Open. |
|
|
|
|
|
|
| |||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Keyswitch (See note below) |
| 9 |
|
| |||||
|
|
| Value |
| Zone |
|
|
|
|
|
| Default Values |
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Fire Zone with verification |
| *0 |
|
| |||||||||||||||||
|
|
|
| Address |
| (Will be forced to different values when in |
|
|
|
|
|
| ||||||||||||||||||||||
|
|
| (fill in) |
| Funct. |
|
|
|
|
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
| Commercial Fire Mode. See section 10.18.3) |
|
|
| Fire Zone w/out verification |
| *1 |
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
| 1 | 0001 | 2 | = Steady alarm output, alarm on short and open. |
|
| Waterflow |
|
|
| *2 |
|
| |||||||||||||||||
|
|
|
|
|
|
|
| 3 | = Entry/exit delay 1. |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
| 0002 |
|
| Supervisory |
|
|
| *3 |
|
| ||||||||||||||||||
|
|
|
|
| 2 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
| 4 | = Entry/exit delay 2. |
|
| Entry/Exit Delay Cancel 1 |
| *4 |
|
| ||||||||||||||||||
|
|
|
|
| 3 | 0003 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
| Entry/Exit Delay Cancel 2 |
| *5 |
|
| |||||||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. |
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
| 4 | 0004 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
| 5 | = Interior entry/exit follower. |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
| 5 | 0005 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
| 6 | = Interior home/away. |
|
|
|
|
|
|
|
|
|
| 9 |
| |||||||||||||
|
|
|
|
| 6 | 0006 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
| 7 | = Interior Instant. |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
| 7 | 0007 | 2 | = Steady alarm output, alarm on short and open. | Note: If digit 2 = 9 (keyswitch), use |
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
| 2 | = |
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
|
| this chart for digit 1. |
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
| 8 | 0008 | 7 = Pulsing alarm output, alarm on short, trouble on open. |
|
|
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
| *0 = Fire zone with verification. |
|
| Select Option |
| DD |
|
|
| ||||||||||||||||||
|
|
|
|
| 9 | 0009 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
| Single |
|
| 0 |
|
|
| |||||||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. |
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
| 10 | 0010 | 2 | = Steady alarm output, alarm on short and open. | Single |
|
| 1 |
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
| 11 | 0011 | All |
|
| 2 |
|
|
| |||||||||||||||||||||
|
|
|
|
| 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
| |||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. | All |
|
| 3 |
|
|
| ||||||||||||||||||
|
|
|
|
| 12 | 0012 | 2 | = Steady alarm output, alarm on short and open. |
|
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. | An open loop will always produce |
|
| ||||||||||||||||||||||
|
|
|
|
| 13 | 0013 | 2 | = Steady alarm output, alarm on short and open. |
|
| ||||||||||||||||||||||||
|
|
|
|
| a steady alarm response. |
|
|
|
|
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
|
| 1 | = Perimeter Instant. |
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
140014 2 = Steady alarm output, alarm on short and open.
1= Perimeter Instant.
150015 2 = Steady alarm output, alarm on short and open.
1= Perimeter Instant.
160016 2 = Steady alarm output, alarm on short and open.
to | to | 1 = Perimeter Instant. |
30 | 0030 |
|