Bosch Appliances DS7447E Zone Problems Continued, Symptom, Probable Cause, Possible Solution

Models: DS7445I DS7447 DS7400XI DS7447E

1 100
Download 100 pages 4.36 Kb
Page 89
Image 89
Zone Problems (Continued)

Zone Problems (Continued)

 

Symptom

 

 

 

Probable Cause

 

Possible Solution

 

 

 

 

 

 

Zones 9 and above show Not Ready,

a)

The multiplex expansion module is not

a)

Make sure the multiplex expansion module is

Zone Trouble.

 

 

 

 

installed properly.

 

seated properly in the upper pins on the

 

 

 

 

 

 

 

 

DS7400Xi circuit board.

 

Never

disconnect

the

b)

Multiplex wiring is missing or is not

b)

Check wiring and perform a system reset.

 

power

when

in

the

 

programming

mode.

 

installed properly.

 

 

 

Always disconnect the

c)

8-Input remote module DIP switches

c)

Correctly set the DIP switches for the 8-Input

 

 

Multiplex Bus or have the

 

DS7430 or DS7436 in

 

are not set properly.

 

remote modules.

 

the

 

disable

d)

8-Input remote module covers are

d)

Replace covers or install the tamper bypass

 

programming

mode

 

when

powering up

or

 

removed.

 

jumper.

 

down.

 

 

 

e)

The BusLoc® code is set incorrectly or

e)

BusLoc® can not be used with 8-Input remote

 

 

 

 

 

 

 

 

 

 

 

has not been programmed into

 

modules. If using 8-Input modules, remove the

 

 

 

 

 

 

modules.

 

BusLoc® code.

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

If using two-input remote modules or the

 

 

 

 

 

 

 

 

DS7465, be sure to use BusLoc® when

 

 

 

 

 

 

 

 

programming. If not using BusLoc®, be sure to

 

 

 

 

 

 

 

 

remove the BusLoc® code from address 9999.

 

 

 

 

 

f)

Zone Programming is incorrect.

f)

Program as a multiple zone input for DS7432 or

 

 

 

 

 

 

DS7460, a single zone input for contacts and

 

 

 

 

 

 

 

 

sensors, or program as a DS7465.

 

 

 

 

 

g)

Multiplex module not programmed.

g)

Program the module.

 

 

 

 

 

 

 

 

 

 

 

 

h)

Multiplex Bus voltage is 12VDC or

h)

Two modules are programmed with the same

 

 

 

 

 

 

address. The problem will only occur when both

 

 

 

 

 

 

greater. (Normal is approximately 8 to

 

modulees are off normal. Isolate the duplicate

 

 

 

 

 

 

10VDC.)

 

module by disconnecting sections of the bus

 

 

 

 

 

 

 

 

and performing a [PIN] + [System Reset].

 

 

 

 

 

 

 

 

Reprogram modules.

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

The system is in the programming mode. Exit

 

 

 

 

 

 

 

 

the programming mode.

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

Zones have been added to a system protected

 

 

 

 

 

 

 

 

by Busloc®. Clear Busloc®.

 

 

 

 

 

i)

Multiplex Bus voltage is 5VDC or less.

i)

There is a short on the multiplex bus.

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

There is a bad module on the bus.

 

 

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

One or more modules on the bus are connected

 

 

 

 

 

 

 

 

backwards - reverse polarity.

 

 

 

 

Invisible or silent zone activates

 

(Normal is approximately 8 to 10VDC.)

Program the output to follow zone alarms (6).

alarm output.

 

 

 

The output is programmed as “latch on

 

 

 

 

 

 

 

alarm” (0).

 

 

Keypad displays Fire Trouble, but

A ground fault condition exists.

See system trouble: Ground fault.

does not indicate any zones.

 

 

 

 

 

 

 

 

Keypad displays Not Ready, but no

An invisible zone is not ready.

Press [PIN] + [OFF] to display the zone number of

zone number is displayed.

 

 

 

 

the invisible zone that is not ready.

 

 

 

 

 

 

 

 

 

15.4General System Problems

Symptom

Probable Cause

 

Possible Solution

 

 

 

 

How to set the programming values

Enter a value of 01 in address 4058.

Caution:

Only enter a value of 01 in address

to the factory default.

 

 

4058 when you are sure you want to

 

 

 

default the programming. Doing so will

 

 

 

immediately erase all programming.

 

 

 

 

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01 Page 89