1.18Options
• DS7412: RS232 Serial Interface module.
The DS7412 module allows the panel to send event information, in an ASCII format, directly to a serial printer or computer. In addition, the interface allows the direct connection of a computer to the panel for programming via the WDSRP programming software.
• Current Draw= 25 mA; 35 mA with LEDs on.
•DS7416i: Advanced Radio Communications Module provides a means of communicating alarm and supervision signals using the Motient radio network. This can
be a replacement for, or a complement to, the standard digital communicator.
•Current draw = 127 mA Standby and Alarm.
•DS7420i: Dual Phone Line/Bell Supervision Module (1 per system).
The DS7420i allows the control to be used in NFPA 72 installations. It provides two supervised 12.0 VDC signaling outputs, one Class A (Style D) input zone, and dual phone line transmission and supervision.
•Current Draw = 20 mA Standby; 140 mA Alarm.
•DS7430: Multiplex Expansion Module (1 per system).
The DS7430 provides a two-wire multiplex bus for the connection of additional remote zones. It also supplies up to 200 mA for 4-wire multiplex devices such as the DS7432.
•Current Draw = 65 mA, Standby; 65 mA, Alarm.
•DS7432: 8-Input Remote Module (up to 30 per system. Requires a DS7430 or DS7436 Multiplex Expansion Module).
The DS7432 provides a means of monitoring conventional Normally Open or Normally Closed contacts. It reports their status to the control panel as multiplex addresses. It occupies eight multiplex zones on the system and can monitor up to eight separate loops. It will support 4-wire smoke detectors.
•Current Draw = 10 mA; Standby. 10 mA, Alarm.
•DS7433: 8-Input Direct Module (1 per system. Can not be used with the DS7430 or DS7436 Multiplex Expansion Modules).
The DS7433 provides a means of expanding the system to include eight additional hard-wired zones. Each zone can support up to twenty 2-wire smoke detectors (can also support 4-wire smoke detectors).
•Current Draw = 65 mA, Standby; 80 mA, Alarm. Add 15 mA for each additional zone in alarm.
•DS7436: Multiplex Expansion Module. (1 per system.)
The DS7436 provides two two-wire multiplex buses for the connection of up to 120 remote points. It also supplies 200 mA per bus.
•Current Draw = 130 mA, Standby or Alarm.
•DS7445/DS7445i: Control Station. (15 Keypads max. per system). The DS7445/DS7445i is an LED keypad which has LEDs representing the first 8 zones of the system. It displays information on various control panel functions. A built in sounder is used as an interior warning device and to annunciate keystroke entries.
•Current Draw = 75 mA, Standby; 75 mA, Alarm.
•DS7447/DS7447E: Control Station. (15 Keypads max. per system)
The DS7447/DS7447E is an Alpha-Numeric LCD keypad. It displays information on various control panel functions. A built-in sounder is used as an interior warning device and to annunciate keystroke entries.
•Current Draw = 100 mA, Standby; 100 mA, Alarm.
•Keypad Access Output: The DS7447/DS7447E Alpha Keypad will provide a ten (10) second access relay output if equipped with the optional K800 Relay. The relay will energize at the keypad if the user has a master, unlimited, general, or access PIN. The output will change only if the user has access to the partition assigned to the keypad. See the DS7445/DS7447 Keypad Installation Instructions (P/N: 22235) or the DS7445/DS7445i/DS7447E Installation Instructions (P/N: 4998138630) for wiring information.
•DS7448: Control Station. (15 Keypads max. per system) The DS7448 is a four-wire LCD annunciator keypad. It has a Silence key and a Reset key used for controlling annunciator and control panel operation, a Keylock Switch that can be used to lock out the annunciator to prevent unwanted silencing or resetting of the control panel, and a two-line, 16-character Display capable of showing all messages normally displayed on a DS7447/ DS7447E keypad.
•Current Draw = 80 mA, Standby; 100 mA, Alarm
•DS7450: Flush Mount Single Multiplex Contact Point (requires a DS7430 Multiplex Expansion Module).
The DS7450 is intended as a replacement for conventional dry contacts, and to report an actual multiplex address to the control panel. Occupies 1 zone.
•Current Draw = 350 μA, Standby; 350 μA, Alarm.
•DS7452: Surface Mount Single Multiplex Contact Point (requires a DS7430 Multiplex Expansion Module).
The DS7452 is intended as a replacement for conventional dry contacts, and to report an actual multiplex address to the control panel. Occupies 1 zone.
•Current Draw = 350 μA, Standby; 350 μA, Alarm.
•DS7455: Surface Mount Single Multiplex Contact Point (requires a DS7430 Multiplex Expansion Module). The DS7455 is intended as a replacement for conventional dry contacts, and to report an actual multiplex address to the control panel. Occupies 1 zone.
•Current Draw = 350 µA, Standby; 350 µA, Alarm.
•DS7457: Single Zone Multiplex Input Module (requires a DS7430 Multiplex Expansion Module).
The DS7457 provides a means of monitoring conventionally Normally Open or Normally Closed contacts. It reports their status to the control panel as multiplex addresses. It occupies one multiplex zone on the system and can monitor one loop. It also includes a tamper loop.
•Current Draw = 350 μA, Standby; 350 μA, Alarm.