Bryant manual PERFORMANCE DATA — 549B, 549C cont, Heater Module

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 116
Image 116
Heater Module

549B, 549C

PERFORMANCE DATA — 549B, 549C (cont)

ACCESSORY ELECTRIC HEATERS STATIC PRESSURE* (in. wg) — 549B036-072 AND 549C024-060

 

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

 

600

900

1200

1400

1600

 

1800

2000

2200

2400

2600

 

 

 

1

Heater Module

0.03

0.05

0.07

0.09

0.09

 

0.10

0.11

0.11

0.12

0.13

2

Heater Modules

0.14

0.15

0.16

0.16

0.16

 

0.17

0.17

0.17

0.18

0.18

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.

ACCESSORY ELECTRIC HEATERS STATIC PRESSURE* (in. wg) — 549B090-120

 

COMPONENT

 

 

 

 

 

CFM

 

 

 

 

 

2250

2500

3000

3500

4000

 

4500

5000

5500

6000

6250

 

 

 

1

Heater Module

0.02

0.03

0.05

0.07

0.08

 

0.10

0.12

0.14

0.16

0.17

2

Heater Modules

0.03

0.05

0.07

0.09

0.12

 

0.14

0.16

0.19

0.21

0.20

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.

ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE* (in. wg) — 549B036-072 AND 549C024-060

COMPONENT

 

 

 

 

CFM

 

 

 

1250

1500

1750

2000

 

2250

2500

2750

3000

 

 

Vertical EconoMi$er2 and EconoMi$erIV

0.045

0.065

0.08

0.12

 

0.145

0.175

0.22

0.255

Horizontal EconoMi$er2 and EconoMi$erIV

0.1

0.125

 

0.15

0.18

0.225

0.275

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.

ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE* (in. wg) — 549B090-120

COMPONENT

 

 

 

 

 

 

CFM

 

 

 

 

 

 

2250

2500

2750

3000

3250

3500

3750

4000

4250

4500

4750

5000

5250

6250

 

Vertical EconoMi$er2 and EconoMi$erIV

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

Horizontal EconoMi$er2 and EconoMi$erIV

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to deter- mine blower rpm and watts.

NOTE: The rooftop unit return air configuration determines the economizer configuration (verti- cal or horizontal).

116

Page 116
Image 116