Bryant 549C manual ELECTRIC HEATING CAPACITIES - 548F090-120, PERFORMANCE DATA — 548F cont

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 53
Image 53
ELECTRIC HEATING CAPACITIES — 548F090-120

PERFORMANCE DATA — 548F (cont)

ELECTRIC HEATING CAPACITIES — 548F090-120

UNIT

UNIT VOLTAGE

ACCESSORY

ELECTRIC HEATER

SINGLE POINT BOX

 

 

PART NUMBER

PACKAGE NO.

 

 

548F

(60 Hz)

 

kW

 

 

 

CRHEATER---A00

CRSINGLE---A00

 

 

 

 

 

 

 

 

 

 

7.8/

9.6/10.4

017

007

 

 

 

208/230/240

12.0/14.7/16.0

010

007

 

 

 

18.6/22.8/24.8

011

009

 

 

 

(3 phase)

 

 

 

24.0/29.4/32.0

012

009

 

 

 

 

 

 

 

 

31.8/39.0/42.4*

012 and 017

013

 

 

090

 

12.8/13.9

016

006

 

 

460/480

15.2/16.5

013

006

 

 

 

25.6/27.8

014

008

 

 

 

(3 phase)

 

 

 

30.4/33.0

015

008

 

 

 

 

 

 

 

 

38.4/41.7*

014 and 016

010

 

 

 

575

 

17.0

018

006

 

548F

 

(3 phase)

 

34.0

019

006

 

 

 

7.8/

9.6/10.4

017

012

 

 

208/230/240

12.0/14.7/16.0

010

012

 

 

 

24.0/29.4/32.0

012

015

 

 

 

(3 phase)

 

 

 

31.8/39.0/42.4*

012 and 017

017

 

 

 

 

 

 

 

 

37.6/46.2/50.0*

010 and 012

017

 

 

120

 

15.2/16.5

013

011

 

 

 

 

 

460/480

25.6/27.8

014

014

 

 

 

30.4/33.0

015

014

 

 

 

(3 phase)

 

 

 

38.4/41.7*

014 and 016

016

 

 

 

 

 

 

 

 

45.9/50.0*

013 and 015

016

 

 

 

575

17.0

018

011

 

 

 

34.0

019

014

 

 

 

(3 phase)

 

 

 

51.0*

018 and 019

016

 

 

 

 

 

 

*Two heater packages required to provide kW indicated.

NOTES:

1.The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.

2.To determine heater kW at voltages other than those shown in table, use the following formula:

Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kW new = 16 kW (215/240)2

kW new = 12.8 kW (rating at 215 v)

53