ELECTRICAL DATA — 548F (cont)

548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)

 

 

 

 

 

VOLTAGE

COMPRESSOR

 

 

 

ELECTRIC

POWER SUPPLY

DISCONNECT

 

 

UNIT

NOMINAL

IFM

RANGE

 

(each)

OFM

IFM

 

 

HEAT*

 

SIZE†

 

 

 

 

 

 

 

 

 

 

548F

V-PH-Hz

TYPE

Min

Max

RLA

 

LRA

FLA

FLA

Nominal

 

FLA

MCA

MOCP

FLA

 

LRA

 

 

 

 

 

 

 

 

kW**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25.5

30††

27

 

145

 

 

 

 

 

 

 

 

 

 

 

 

16.5

 

 

19.8

50.3

60††

50

 

165

 

 

 

 

STD

414

508

8.6

 

59.6

0.7

2.6

27.8

 

 

33.4

67.3

70

65

 

178

 

 

 

 

 

33.0

 

 

39.7

75.2

80

73

 

185

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

 

50.2

88.3

90

85

 

195***

 

 

 

 

 

 

 

 

 

 

 

 

50.0

 

 

60.1

85.6

90

96

 

205***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26.3

30††

28

 

185

 

 

 

 

 

 

 

 

 

 

 

 

16.5

 

 

19.8

51.1

60††

51

 

204

 

 

 

460-3-60

ALT

414

508

8.6

 

59.6

0.7

3.4

27.8

 

 

33.4

68.1

70

66

 

218

548F

 

 

 

33.0

 

 

39.7

76.0

80

73

 

224

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

 

50.2

89.1

90

86

 

235***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50.0

 

 

60.1

86.4

90

97

 

245***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30.3

35††

32

 

179

 

 

 

 

 

 

 

 

 

 

 

 

16.5

 

 

19.8

55.1

60††

55

 

198

 

 

120

 

HIGH-STATIC

414

508

8.6

 

59.6

0.7

7.4

27.8

 

 

33.4

72.1

80

71

 

212

 

 

(10 Tons)

 

 

33.0

 

 

39.7

80.0

80

78

 

218

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41.7

 

 

50.2

93.1

100

90

 

229***

 

 

 

 

 

 

 

 

 

 

 

 

50.0

 

 

60.1

90.4

100

102

 

239***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20.5

25††

22

 

120

 

 

 

 

STD

518

632

6.9

 

49.4

0.7

2.6

17.0

 

 

17.1

41.8

45††

41

 

137

 

 

 

 

 

34.0

 

 

34.1

63.1

70

61

 

154

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

 

51.2

71.7

80

80

 

171***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21.1

25††

22

 

151

 

 

 

575-3-60

ALT

518

632

6.9

 

49.4

0.7

3.4

17.0

 

 

17.1

42.5

45††

42

 

168

 

 

 

 

34.0

 

 

34.1

63.7

70

62

 

185

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

 

51.2

72.3

80

81

 

202***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24.3

25††

26

 

146

 

 

 

 

HIGH-STATIC

518

632

6.9

 

49.4

0.7

7.4

17.0

 

 

17.1

45.7

50††

46

 

163

 

 

 

 

 

34.0

 

 

34.1

66.9

70

65

 

180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51.0

 

 

51.2

75.5

80

85

 

198***

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor Fan Motor

RLA — Rated Load Amps

*Heaters are field installed only.

†Used to determine minimum disconnect size per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

††Fuse or HACR circuit breaker.

***Optional disconnect switch is unavailable.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

= 1371 3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

POWER EXHAUST

MCA

MCA

MCA

MOCP

(for separate

PART NO.

(230 v)

(460 v)

(575 v)

power source)

 

 

 

 

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

N/A — Not available

NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP.

Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula:

MCA New = MCA unit only + MCA of Power Exhaust

For example, using a 548F060 unit with MCA = 35.6 and MOCP = 40, with CRPWREXH030A01 power exhaust.

MCA New = 35.6 amps + 1.6 amps = 37.2 amps

If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 40 amps and the MCA New is below 40; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the power exhaust should be 15 amps per NEC.

64