FAN RPM AT MOTOR PULLEY SETTINGS*

PERFORMANCE DATA — 549B, 549C (cont)

FAN RPM AT MOTOR PULLEY SETTINGS*

UNIT

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

0

1/2

1

11/2

2

21/2

3

31/2

4

41/2

5

51/2

6

 

549C024

936

906

877

847

817

788

758

728

698

669

639

549B, 549C036†

1044

1008

971

935

898

862

826

789

753

716

680

549B036**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

549B, 549C048†

1185

1144

1102

1061

1019

978

936

895

853

812

770

549B048**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

549B, 549C060†

1460

1425

1390

1355

1319

1284

1249

1214

1179

1144

1108

1073

1038

549B060**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

549B072†

1585

1538

1492

1445

1399

1352

1305

1259

1212

1166

1119

549B072**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

549B090†

950

930

905

885

865

840

820

795

775

750

730

549B090**

1080

1060

1035

1015

990

970

950

925

905

880

860

549B102†

1085

1061

1036

1012

987

963

938

914

889

865

840

549B102**

1080

1058

1036

1014

992

970

948

926

904

882

860

549B120†

1080

1060

1035

1015

990

970

950

925

905

880

860

549B120**

1219

1195

1170

1145

1120

1095

1071

1046

1021

996

972

947

922

*Approximate fan rpm shown.

 

 

 

 

 

 

 

 

 

 

 

 

 

†Indicates standard motor and drive package. **Indicates high-static motor and drive package.

INDOOR-FAN MOTOR PERFORMANCE — STANDARD MOTORS

UNIT

UNIT

MAXIMUM

MAXIMUM

MAXIMUM

MOTOR

549B, 549C

VOLTAGE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

EFFICIENCY

024

ALL

0.58

580

2.0

75.0

 

208/230-1-60

1.20

1195

4.9

75.0

036

208/230-3-60

1.20

1195

4.9

75.0

 

460-3-60

2.3

75.0

 

 

 

 

208/230-1-60

1.20

1195

4.9

75.0

048

208/230-3-60

1.20

1195

4.9

75.0

 

460-3-60

2.3

75.0

 

 

 

 

208/230-1-60

1.30

1290

7.6

74.0

060

208/230-3-60

2.40

2120

6.0

84.0

 

460-3-60

3.0

84.0

 

 

 

072

208/230-3-60

2.40

2120

6.0

84.0

460-3-60

3.0

84.0

 

 

 

090,

208/230-3-60

2.90

2615

8.6

80.0

102

460-3-60

2.90

2615

3.9

80.0

120

208/230-3-60

3.70

3313

11.7

85.0

460-3-60

3.70

3313

5.5

85.0

 

549B, 549C

INDOOR-FAN MOTOR PERFORMANCE — HIGH-STATIC MOTORS

UNIT

UNIT

MAXIMUM

MAXIMUM

MAXIMUM

MOTOR

549B,549C

VOLTAGE

CONTINUOUS BHP*

OPERATING WATTS*

AMP DRAW

EFFICIENCY

036

208/230-3-60

2.40

2120

6.0

75

460-3-60

3.0

75

 

 

 

048

208/230-3-60

2.40

2120

6.0

75

460-3-60

3.0

75

 

 

 

060

208/230-3-60

2.90

2615

8.6

84

460-3-60

3.9

84

 

 

 

072

208/230-3-60

2.90

2615

8.6

84

460-3-60

3.9

84

 

 

 

090,

208/230-3-60

3.70

3313

11.7

80

102

460-3-60

5.5

80

 

 

120

208/230-3-60

5.25

4400

17.3

85

460-3-60

8.5

85

 

 

 

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.