Bryant 549C manual ELECTRIC HEATING CAPACITIES — 542J150,180, PERFORMANCE DATA — 542J cont

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 151
Image 151
ELECTRIC HEATING CAPACITIES — 542J150,180

PERFORMANCE DATA — 542J (cont)

ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180

ACCESSORY/FIOP

UNIT SIZE

UNIT VOLTAGE

kW

 

 

 

 

CFM

 

 

 

3750

4500

5000

5600

 

6000

6250

7200

7500

 

 

 

 

 

 

 

208/230-3-60

14-34

0.05

0.05

0.07

0.08

 

0.09

0.09

0.11

0.12

 

150

 

42,56

0.06

0.06

0.08

0.10

 

0.12

0.13

0.16

0.17

 

460-3-60

15,32

0.05

0.05

0.07

0.08

 

0.09

0.09

0.11

0.12

 

 

 

55

0.06

0.06

0.08

0.10

 

0.12

0.13

0.15

0.15

Electric Heaters

 

575-3-60

37

0.06

0.06

0.08

0.10

 

0.12

0.13

0.15

0.17

 

208/230-3-60

26,34

*

*

*

0.08

 

0.09

0.09

0.11

0.12

 

 

 

 

180

 

42,59

 

 

 

0.10

 

0.12

0.13

0.16

0.17

 

460-3-60

32,55

*

*

*

0.08

 

0.09

0.09

0.11

0.12

 

 

 

 

 

 

 

0.10

 

0.12

0.13

0.15

0.17

 

 

575-3-60

50

*

*

*

0.13

 

0.15

0.16

0.20

0.21

EconoMi$erIV and

150,180

All

0.03

0.04

0.05

0.06

 

0.07

0.07

0.08

0.10

EconoMi$er2

 

 

 

 

 

 

 

 

 

 

 

 

 

Glycol Coil

150,180

All

0.16

0.18

0.25

0.31

 

0.35

0.37

0.44

0.46

LEGEND

FIOP — Factory-Installed Option

*Units with electric heat are not designed to operate at these ranges.

NOTES:

1. Heaters are rated at 208/240 v, 480 v, and 600 v.

2.The static pressure must be added to external static pressure. The sum and the indoor-air section entering-air cfm should then be used in conjunction with the Fan Performance table to determine blower rpm, bhp, and watts.

ELECTRIC HEATING CAPACITIES — 542J150,180

 

 

HEATER kW

 

HEATER

% HEAT

MAXIMUM

UNIT 542J

 

Unit Voltages

 

 

 

STAGES

PER STAGE

STAGES*

 

208

230

460

575

 

 

 

 

150

14

19

15

1

100

1

26

34

32

2

50/50

2

 

42

56

55

37

2

33/67

3

180

26

34

32

2

50/50

2

42

56

55

2

33/67

3

 

50

2

50/50

4

*Maximum number of stages using accessory outdoor-air thermostats.

NOTE: Heaters are rated at 208 v, 240 v, 480 v, and 600 v. See multipli- cation factors table on page 152.