MODEL NUMBER NOMENCLATURE — 542J150,180 UNITS

542J E X 150 000 AB H B

542J – High-Efficiency Rooftop Units

Electric Heat Pumps

Voltage Designation

E – 460-3-60

P – 208/230-3-60

T – 575-3-60

Heat Type

X – No Heat Installed

Nominal Cooling Capacity

150 – 12 Tons

180 – 15 Tons

Electric Heaters

 

000 – No Factory-Installed Electric Heaters

 

Accessory Field-Installed Electric Heaters

a50-8040

Available

 

Quality Assurance

Certified to ISO 9001:2000

ARI* CAPACITY RATINGS

548F036-060

Fan Drive Position

(Standard Motor)

B – Standard Low-Medium

Fan Drive Static Capability

D – Alternate High Fan

Drive Static Capability

Factory-Installed Outdoor Air Upgrade Options

C – Economizer

H – 25% Manual Damper

Design Series Code

AB – Economizer Design Change

 

 

 

COOLING

 

 

HEATING

 

 

UNIT

NOMINAL

 

 

 

(High Temp)

 

SOUND

 

 

 

 

 

 

548F

TONS

Net Capacity

 

 

SEER†

Capacity

 

 

RATING

 

 

 

 

 

HSPF

(decibels)

 

 

(Btuh)

 

Belt

 

Direct

(Btuh)

 

 

 

 

Drive

 

Drive

 

 

 

 

 

 

 

 

 

 

 

 

036

3

35,600

 

10.20

 

10.00

34,400

 

6.7

84

048

4

46,500

 

10.00

 

9.70

46,500

 

7.0

80

060

5

57,000

 

10.00

 

9.90

57,000

 

7.5

82

548F072-120

 

 

COOLING

 

HEATING

 

HEATING

 

 

SOUND

UNIT

NOMINAL

 

(High)

 

(Low)

 

 

 

 

 

 

IPLV**

RATING

548F

TONS

 

 

 

 

 

 

 

 

Net Capacity

EER

Capacity

 

COP

Capacity

 

COP

 

(decibels)

 

 

(Btuh)

(Btuh)

 

(Btuh)

 

 

 

 

 

 

 

 

 

 

 

072

6

70,000

9.05

72,400

 

3.20

42,000

 

2.14

—

82

090

71/2

86,000

9.00

78,000

 

3.00

39,000

 

1.80

9.3

86

120

10

112,000

9.00

105,000

 

3.10

59,000

 

2.00

9.0

84

 

LEGEND

COP

— Coefficient of Performance

db

— dry bulb

EER

— Energy Efficiency Ratio

HSPF — Heating Seasonal Performance Factor

IPLV

— Integrated Part-Load Values

SEER — Seasonal Energy Efficiency Ratio

wb

— wet bulb

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 60,000 Btuh or less. **The IPLV applies only to 2-stage cooling heat pump units.

NOTES:

1.Rated in accordance with ARI Standards 210/240-95 and 270-95.

2.Ratings are net values, reflecting the effects of circulating fan heat.

3.ALL the 548F036-060 units are in compliance with ASHRAE 90.1 2001 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website: http://solstice.crest.org/efficiency/bcap to determine if compliance with this standard pertains to a given geographical area of the United States.

4. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F db, 43 F wb outdoor entering-air temperature.

Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F db, 15 F wb outdoor entering-air temperature.

5

Page 5
Image 5
Bryant 549C manual Model Number Nomenclature 542J150,180 Units, ARI* Capacity Ratings, 548F036-060, 548F072-120