Bryant 549C manual PERFORMANCE DATA — 542J, Cooling Capacities

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 146
Image 146
PERFORMANCE DATA — 542J

PERFORMANCE DATA — 542J

COOLING CAPACITIES

542J150 (121/2 Tons)

Temp (F)

 

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

 

Outdoor

 

3750/0.04

 

 

4500/0.05

 

 

 

5000/0.05

 

 

 

5625/0.06

 

 

6250/0.07

 

Entering Air

 

 

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

 

 

(Edb)

72

67

62

72

67

62

 

72

67

62

 

72

67

62

72

67

62

 

 

 

 

 

75

 

TC

167.0

154.0

140.0

171.0

158.0

144.0

 

173.0

159.0

146.0

 

171.0

162.0

148.0

173.0

161.0

151.0

 

SHC

79.6

100.0

120.0

85.0

108.0

131.0

 

87.5

114.0

138.0

 

94.5

120.0

146.0

97.7

127.0

150.0

 

 

kW

10.00

9.77

9.50

10.10

9.87

9.61

 

10.20

9.93

9.68

 

10.20

10.00

9.74

10.20

10.00

9.80

85

 

TC

160.0

148.0

133.0

164.0

151.0

137.0

 

167.0

154.0

140.0

 

168.0

155.0

143.0

166.0

157.0

146.0

 

SHC

77.6

98.9

118.0

82.0

107.0

129.0

 

86.1

113.0

136.0

 

89.6

118.0

142.0

95.3

125.0

146.0

 

 

kW

11.10

10.80

10.40

11.20

10.90

10.60

 

11.30

11.00

10.70

 

11.30

11.00

10.80

11.30

11.10

10.80

95

 

TC

155.0

141.0

127.0

157.0

144.0

131.0

 

160.0

146.0

133.0

 

161.0

149.0

137.0

163.0

149.0

140.0

 

SHC

76.1

96.3

115.0

80.3

105.0

126.0

 

84.4

110.0

132.0

 

86.5

117.0

137.0

91.7

121.0

140.0

 

 

kW

12.20

11.80

11.40

12.20

11.90

11.50

 

12.40

12.00

11.60

 

12.40

12.10

11.80

12.50

12.10

11.90

105

 

TC

147.0

133.0

120.0

150.0

137.0

124.0

 

152.0

138.0

127.0

 

153.0

140.0

131.0

154.0

141.0

134.0

 

SHC

73.6

93.3

112.0

78.5

102.0

123.0

 

81.6

108.0

127.0

 

85.1

114.0

131.0

88.6

120.0

134.0

 

 

kW

13.20

12.70

12.30

13.30

12.90

12.50

 

13.40

13.00

12.60

 

13.50

13.10

12.80

13.50

13.10

12.90

115

 

TC

140.0

126.0

112.0

141.0

129.0

118.0

 

144.0

130.0

121.0

 

144.0

131.0

125.0

146.0

133.0

128.0

 

SHC

71.4

90.3

109.0

75.1

99.1

117.0

 

78.9

104.0

121.0

 

81.9

110.0

125.0

87.0

117.0

128.0

 

 

kW

14.20

13.70

13.20

14.30

13.90

13.50

 

14.40

14.00

13.70

 

14.50

14.00

13.90

14.60

14.10

14.00

125

 

TC

131.0

118.0

105.0

134.0

120.0

111.0

 

135.0

122.0

115.0

 

137.0

123.0

118.0

136.0

124.0

121.0

 

SHC

68.1

87.6

105.0

73.5

96.4

111.0

 

75.7

102.0

115.0

 

80.7

108.0

118.0

83.4

113.0

121.0

 

 

kW

15.20

14.70

14.10

15.40

14.90

14.50

 

15.40

14.90

14.70

 

15.60

15.00

14.90

15.60

15.10

15.00

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)

TC — Gross Total Capacity (1000 Btuh)

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb

= tedb

sensible capacity (Btuh)

1.10 x cfm

 

 

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb = Enthalpy of air entering indoor coil

3.SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

FACTOR

81

82

83

84

85

over 85

(BF)

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

.10

.98

1.96

2.94

3.92

4.90

Use formula

.20

.87

1.74

2.62

3.49

4.36

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

542J180 (15 Tons)

Temp (F)

 

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

 

Outdoor

 

4500/0.06

 

 

5250/0.08

 

 

 

6000/0.10

 

 

 

6750/0.10

 

 

7500/0.12

 

Entering Air

 

 

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

 

72

67

62

 

72

67

62

72

67

62

 

 

 

 

 

75

 

TC

210.0

192.0

173.4

216.0

196.6

178.4

 

220.0

202.0

182.2

 

222.0

204.0

185.6

224.0

206.0

190.2

 

SHC

100.6

125.2

148.2

106.0

134.0

160.6

 

110.6

143.0

172.2

 

115.0

151.2

183.2

120.2

158.2

190.0

 

 

kW

13.58

13.12

12.66

13.76

13.28

12.84

 

13.88

13.44

12.98

 

13.96

13.52

13.10

14.02

13.60

13.26

85

 

TC

202.0

183.0

164.4

208.0

187.8

169.0

 

212.0

191.4

172.8

 

212.0

194.0

177.2

214.0

195.8

182.2

 

SHC

98.0

121.8

144.2

103.8

131.2

156.4

 

109.0

140.0

168.6

 

112.0

148.0

177.0

116.2

155.6

182.2

 

 

kW

14.86

14.32

13.78

15.08

14.52

13.98

 

15.22

14.66

14.14

 

15.26

14.78

14.30

15.34

14.86

14.50

95

 

TC

192.4

173.2

155.0

196.2

177.8

159.2

 

200.0

180.8

163.4

 

202.0

183.4

169.0

204.0

185.4

174.2

 

SHC

94.8

118.0

140.0

100.2

127.4

152.6

 

105.6

136.4

163.4

 

110.6

144.8

169.0

114.2

153.2

173.8

 

 

kW

16.16

15.52

14.88

16.32

15.72

15.10

 

16.48

15.88

15.30

 

16.62

16.00

15.54

16.64

16.12

15.76

105

 

TC

182.0

163.0

145.0

186.4

167.0

149.4

 

188.6

170.0

155.4

 

191.0

172.2

160.8

193.0

173.8

165.2

 

SHC

91.0

114.2

135.2

96.8

123.6

147.6

 

101.8

132.6

155.2

 

107.2

141.2

160.6

112.2

149.6

165.2

 

 

kW

17.36

16.64

15.92

17.58

16.86

16.16

 

17.70

17.04

16.48

 

17.84

17.18

16.74

17.94

17.28

16.96

115

 

TC

171.2

152.4

134.8

175.0

156.2

140.6

 

177.8

158.8

146.8

 

179.4

160.8

152.2

179.6

162.2

156.4

 

SHC

87.4

110.2

130.8

92.6

119.4

140.6

 

98.8

128.2

146.8

 

103.6

136.8

151.8

107.2

144.6

156.2

 

 

kW

18.54

17.72

16.90

18.76

17.94

17.24

 

18.94

18.12

17.60

 

19.02

18.28

17.90

19.04

18.38

18.16

125

 

TC

159.4

141.2

125.0

162.8

143.8

132.0

 

165.6

147.0

137.8

 

166.6

148.8

143.0

168.2

150.0

146.8

 

SHC

83.6

105.8

125.0

89.0

115.0

131.8

 

94.4

123.6

137.8

 

99.8

132.2

142.8

105.0

139.6

146.6

 

 

kW

19.64

18.74

17.88

19.86

19.00

18.34

 

20.00

19.12

18.72

 

20.20

19.28

19.00

20.20

19.40

19.28

542J

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)

TC — Gross Total Capacity (1000 Btuh)

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb

= tedb

sensible capacity (Btuh)

1.10 x cfm

 

 

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb = Enthalpy of air entering indoor coil

3.SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

FACTOR

81

82

83

84

85

over 85

(BF)

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

.10

.98

1.96

2.94

3.92

4.90

Use formula

.20

.87

1.74

2.62

3.49

4.36

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).