Bryant ARI* CAPACITY RATINGS cont, 549C024-060, 549B036-060, 549B072-120, 542J150,180 UNITS

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 6
Image 6
ARI* CAPACITY RATINGS (cont)

ARI* CAPACITY RATINGS (cont)

549C024-060

UNIT

NOMINAL

 

 

 

COOLING

 

 

HEATING (High Temp)

SOUND

549C

TONS

 

 

Net Cap.

 

SEER†

 

 

Cap.

 

HSPF†

RATING

 

 

(Btuh)

 

 

 

(Btuh)

 

(decibels)

024

 

2

 

 

 

24,000

14.0

 

 

 

23,600

 

 

8.10

 

76

036

 

3

 

 

 

37,000

14.0

 

 

 

36,000

 

 

8.10

 

76

048

 

4

 

 

 

46,000

14.0

 

 

 

46,000

 

 

8.00

 

76

060

 

5

 

 

 

58,500

14.0

 

 

 

58,000

 

 

8.00

 

80

 

 

 

 

 

 

 

 

 

549B036-060

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOMINAL

 

 

 

COOLING

 

 

HEATING (High Temp)

SOUND

549B

TONS

 

 

Net Cap.

 

SEER†

 

 

Cap.

 

HSPF†

RATING

 

 

(Btuh)

 

 

 

(Btuh)

 

(decibels)

036

 

3

 

 

 

35,600

13.1

 

 

 

34,800

 

 

7.7

 

76

048

 

4

 

 

 

45,000

13.0

 

 

 

45,000

 

 

7.8

 

76

060

 

5

 

 

 

58,000

13.0

 

 

 

55,000

 

 

7.7

 

80

 

 

 

 

 

 

 

 

 

549B072-120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING

 

HEATING

 

HEATING

SOUND

 

 

UNIT

 

NOMINAL

 

 

(High)

 

(Low)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

549B

 

TONS

 

Net Cap.

 

 

 

Cap.

 

 

 

Cap.

 

 

RATING

 

IPLV

 

 

 

EER

 

 

 

COP

 

COP

(decibels)

 

 

 

 

 

 

(Btuh)

 

 

 

(Btuh)

 

 

(Btuh)

 

 

 

 

 

072

 

6

 

71,000

 

10.5

 

69,000

 

 

3.4

37,000

 

2.2

80

 

090

 

71/2

 

88,000

 

10.3

 

85,000

 

 

3.3

48,000

 

2.2

82

 

10.5

102

 

81/2

 

98,000

 

10.3

 

96,000

 

 

3.3

52,000

 

2.2

110

 

12.7 (100%)

 

 

 

 

 

 

 

 

10.4 ( 50%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

10

 

116,000

 

10.3

 

103,000

 

 

3.3

64,000

 

2.2

84

 

10.4

LEGEND

Cap. — Net Capacity (Btuh)

COP — Coefficient of Performance EER — Energy Efficiency Ratio

HSPF — Heating Seasonal Performance Factor IPLV — Integrated Part-Load Values

SEER — Seasonal Energy Efficiency Ratio

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 60,000 Btuh or less.

NOTE: Rated in accordance with ARI Standard 210/240-94 and 270-

95.Ratings are net values, reflecting effects of circulating fan heat. Supplementary electric heat is not included. Ratings based on:

Cooling Standard: 80 F db (dry bulb), 67 F wb (wet bulb) indoor enter- ing-air temperature and 95 F db outdoor entering-air temperature. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F db, 43 F wb outdoor entering-air temperature.

Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F db, 15 F wb outdoor entering-air temperature.

ALL the 549B units are in compliance with ASHRAE 90.1 2001 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website: http://solstice.crest.org/ efficiency/bcap to determine if compliance with this standard pertains to a given geographical area of the United States.

542J150,180 UNITS

UNIT

 

COOLING

 

 

HEATING-HIGH TEMP

HEATING-LOW TEMP

SOUND

Total

Net

 

 

 

Total

Total

 

Total

Total

 

RATING

542J

Capacity

Cfm

IPLV

EER

Capacity

COP

Capacity

COP

 

kW

kW

kW

(decibels)

 

 

(Btuh)

 

 

 

(Btuh)

 

 

(Btuh)

 

 

 

150

14.3

140,000

4500

12.4

9.8

136,000

12.4

3.2

72,000

10.0

2.1

87

180

18.5

172,000

5200

9.7

9.3

172,000

15.3

3.3

90,000

12.5

2.2

88

LEGEND

COP — Coefficient of Performance db — Dry Bulb EER — Energy Efficiency Ratio ESP — External Static Pressure IPLV — Integrated Part-Load Value wb — Wet Bulb

*Air-Conditioning and Refrigeration Institute.549C024-060549B036-060549B072-120542J150,180 UNITSManual backgroundManual backgroundManual background NOTE: 50HJQ units are rated in accordance with ARI Standard 340-93.

Cooling ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:

ESP: –.35 in. wg

Cooling Standard: 80 F db, 67 wb indoor coil entering-air temperature and 95 F outdoor entering-air temperature.

High-Temp Heating Standard: 70 F db indoor coil entering-air temper- ature and 47 F db, 43 F wb outdoor coil entering-air temperature.

Low-Temp Heating Standard: 70 F db indoor coil entering-air temper- ature and 17 F db, 15 F wb outdoor coil entering-air temperature.

IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.

ALL the 542J units are in compliance with ASHRAE 90.1 2001 Energy Standard for minimum SEER and EER requirements. Refer to state and local codes or visit the following website: http://solstice.crest.org/ efficiency/bcap to determine if compliance with this standard pertains to a given geographical area of the United States.

6

Page 6