FAN PERFORMANCE — VERTICAL DISCHARGE UNITS

PERFORMANCE DATA — 548F (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS

548F036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)

Airflow

 

 

 

Low Speed

 

 

 

 

 

High Speed

 

 

 

 

 

208 v

 

 

230, 460, 575 v

 

208 v

 

 

230, 460, 575 v

(Cfm)

 

 

 

 

 

 

 

 

ESP

Bhp

Watts

ESP

 

Bhp

Watts

ESP

Bhp

Watts

ESP

 

Bhp

Watts

 

 

 

 

900

 

0.67

0.21

253

0.68

 

0.23

277

0.69

0.26

307

0.69

 

0.31

363

1000

 

0.60

0.23

270

0.61

 

0.25

292

0.61

0.27

321

0.63

 

0.32

374

1100

 

0.55

0.24

287

0.56

 

0.26

307

0.57

0.28

335

0.58

 

0.33

385

1200

 

0.51

0.26

304

0.51

 

0.27

323

0.52

0.29

349

0.53

 

0.34

397

1300

 

0.45

0.27

321

0.46

 

0.29

338

0.46

0.31

364

0.47

 

0.34

408

1400

 

0.38

0.29

338

0.41

 

0.30

354

0.43

0.32

378

 

1500

 

0.34

0.30

355

0.36

 

0.31

369

0.38

0.33

392

 

 

LEGEND

 

 

 

 

 

See General Fan Performance notes below.

 

 

 

Bhp — Brake Horsepower Input to Fan

ESP — External Static Pressure (in. wg)

Watts — Input Watts to Motor

548F036 (3 TONS) — ALTERNATE MOTOR AND DRIVE*

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

900

643

0.15

152

768

0.22

 

222

870

0.30

296

958

0.37

373

1037

0.46

454

1000

683

0.19

191

804

0.27

 

268

904

0.35

348

991

0.43

430

1069

0.52

517

1100

725

0.24

237

842

0.32

 

321

939

0.41

407

1025

0.50

496

1102

0.59

588

1200

767

0.29

291

880

0.38

 

382

976

0.48

474

1060

0.57

570

1136

0.67

668

1300

811

0.35

352

920

0.45

 

451

1013

0.55

550

1095

0.66

652

1170

0.76

756

1400

855

0.43

423

960

0.53

 

529

1051

0.64

636

1132

0.75

744

1205

0.86

855

1500

900

0.51

504

1002

0.62

 

617

1090

0.74

731

1169

0.85

846

1242

0.97

963

 

 

 

 

 

 

 

 

 

 

548F036 (3 TONS) — ALTERNATE MOTOR AND DRIVE* (cont)

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

 

 

 

External Static Pressure (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

 

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

900

1110

0.54

538

1177

0.63

 

627

1239

0.72

718

1298

0.82

813

1355

0.92

911

1000

1141

0.61

607

1207

0.70

 

700

1269

0.80

796

1328

0.90

895

1384

1.00

998

1100

1173

0.69

683

1238

0.79

 

781

1300

0.89

883

1358

0.99

987

1200

1205

0.77

768

1270

0.88

 

872

1332

0.98

979

1300

1239

0.87

863

1303

0.98

 

972

1400

1273

0.97

967

 

1500

 

 

 

LEGEND

See General Fan Performance notes below.

Bhp

Brake Horsepower Input to Fan
NOTES:
Watts

Input Watts to Motor

1.

Boldface indicates field-supplied drive is required.

*Motor drive range: 760 to 1000 rpm. All other rpms require a field-

2.

Maximum continuous bhp is 1.00.

 

 

supplied drive.

548F

GENERAL FAN PERFORMANCE NOTES

1.Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nui- sance tripping or premature motor failure. Unit warranty will not be affected. For additional information on motor performance, refer to Indoor Fan Motor Performance table on page 54.

2.Values include losses for filters, unit casing, and wet coils. See Accessory/FIOP Static Pressure tables on page 50 for accessory static pressure information.

3.Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details.

4.Interpolation is permissible. Do not extrapolate.

27