Bryant PERFORMANCE DATA — 549B, 549C cont, COOLING CAPACITIES cont, Bypass, 1.04, 2.07, 4.14

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 86
Image 86
Manual background

PERFORMANCE DATA — 549B, 549C (cont)

COOLING CAPACITIES (cont)

549C060 (5 Tons)

Temp (F)

 

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

 

Outdoor

 

1500/0.05

 

 

1750/.05

 

 

2000/.07

 

 

2500/.08

 

Entering Air

 

 

 

 

 

 

Indoor Entering

Air — Ewb (F)

 

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

 

 

 

75

 

TC

56.2

59.2

65

70.3

59.5

61.3

66.9

71.5

62.2

62.9

68.2

72.9

66.1

66.1

70

74.1

 

SHC

54

49.5

41.1

32.3

57.1

54.2

44.4

33.8

59.8

58.4

47.4

35.6

63.5

63.5

53.3

38.4

 

 

kW

3.17

3.19

3.19

3.22

3.18

3.18

3.2

3.23

3.19

3.19

3.21

3.24

3.2

3.2

3.22

3.25

85

 

TC

53.3

56

62.6

68.5

57.2

58.4

64.5

69.9

59.9

60.1

66

70.9

64.1

64.1

67.8

72.6

 

SHC

51.2

48.3

40.4

31.8

55

53.1

43.8

33.6

57.6

57.2

47.1

35.3

61.6

61.6

53.2

38.6

 

 

kW

3.59

3.6

3.62

3.64

3.61

3.61

3.63

3.65

3.61

3.61

3.63

3.66

3.62

3.62

3.64

3.67

95

 

TC

49.1

50.5

59.4

65.8

53.6

53.7

61.3

67.7

56.8

56.8

62.7

68.7

61.5

61.5

64.8

70.5

 

SHC

47.1

46.1

39.3

30.9

51.6

51.1

42.7

33.1

54.7

54.6

46.1

34.8

59.1

59.1

52.6

38.6

 

 

kW

4.02

4.03

4.08

4.1

4.05

4.05

4.09

4.12

4.08

4.07

4.1

4.12

4.09

4.09

4.11

4.14

105

 

TC

44.7

44.6

52.9

62.4

48.8

48.9

55.4

64.2

51.5

51.5

58

65.6

57.8

57.8

60.8

67.3

 

SHC

42.9

42.9

37

29.9

46.9

47

40.8

32.1

49.5

49.5

44.6

34.1

55.6

55.6

51.5

37.9

 

 

kW

4.49

4.49

4.56

4.61

4.53

4.53

4.58

4.63

4.55

4.55

4.6

4.64

4.6

4.6

4.62

4.64

115

 

TC

39.9

40

45.2

56.4

43.9

43.9

47.2

59.5

46

46.2

49.8

61.4

52

51.9

52.6

63.3

 

SHC

38.4

38.4

34.3

28.1

42.2

42.2

38

30.7

44.3

44.4

41.9

33

50

50

48.8

37.1

 

 

kW

4.98

4.98

5.06

5.16

5.05

5.05

5.08

5.18

5.07

5.07

5.11

5.2

5.13

5.13

5.13

5.21

125

 

TC

35.9

35.9

38.4

49

38.6

38.5

39.7

50.9

41.1

41

41.3

52.8

45.1

45.2

45.3

55.6

 

SHC

34.5

34.5

32.1

25.8

37.1

37.1

35.5

28.1

39.5

39.5

39

30.5

43.4

43.5

43.6

35

 

 

kW

5.53

5.53

5.57

5.7

5.58

5.58

5.59

5.72

5.62

5.62

5.62

5.74

5.68

5.67

5.68

5.77

549B, 549C

LEGEND

BF — Bypass Factor Edb — Entering Dry-Bulb Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh) TC — Gross Total Capacity (1000 Btuh)

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb

= tedb

sensible capacity (Btuh)

1.10 x cfm

 

 

tlwb = Wet-bulb temperature corresponding to enthalpy of air leav- ing indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb = Enthalpy of air entering indoor coil

3.SHC is based on 80 F edb temperature of air entering indoor coil. Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

BYPASS

 

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

 

under 75

FACTOR

 

 

 

 

 

 

 

81

82

83

84

85

 

over 85

(BF)

 

 

 

 

Correction Factor

 

.05

1.04

2.07

3.11

4.14

5.18

 

 

.10

.98

1.96

2.94

3.92

4.90

 

Use formula

.20

.87

1.74

2.62

3.49

4.36

 

shown below.

.30

.76

1.53

2.29

3.05

3.82

 

 

Interpolation is permissible.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

86

Page 86
Image 86
Bryant PERFORMANCE DATA — 549B, 549C cont, COOLING CAPACITIES cont, Above 80 F edb, add corr factor x cfm to SHC, 1.04