ELECTRICAL DATA — 549B (cont)

549B036-120 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

 

NOMINAL

VOLTAGE

COMPRESSOR

OFM

 

 

 

 

 

 

 

 

 

MINIMUM UNIT

UNIT

IFM

ELECTRIC HEAT*

POWER SUPPLY

 

 

DISCONNECT

VOLTAGE

RANGE

 

(each)

(each)

 

 

549B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

 

(V-Ph-Hz)

Min

Max

RLA

 

LRA

FLA

FLA

kW†

FLA

MCA

MOCP

FLA

LRA

 

 

 

 

 

 

 

 

 

 

 

 

43.0/ 43.0

45/ 45**

46/ 46

247/247

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

70.1/

74.3

80/

80

71/

75

269/272

 

208/230-3-60

187

254

12.4

 

88.0

1.4

7.5

12.0/16.0

33.3/

38.5

84.6/

91.1

90/100

84/

90

280/285††

 

 

 

 

 

 

 

 

 

18.6/24.8

51.6/

59.7

107.5/117.6

110/125

105/115

298/307††

090

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

126.3/139.3

150/150

122/134

313/324††

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

153.4/170.5

175/175

147/163

335/349††

(71/2 Tons)

 

 

 

 

 

 

 

 

21.4

25**

23

123

 

 

 

 

 

 

 

 

 

13.9

16.7

42.3

45**

42

140

 

460-3-60

414

508

6.4

 

44.0

0.7

3.4

16.5

19.8

46.1

50**

46

143

 

 

 

 

 

 

 

 

 

27.8

33.4

63.1

70

 

61

157

 

 

 

 

 

 

 

 

 

33.0

39.7

71.0

80

 

68

163

 

 

 

 

 

 

 

 

 

41.7

50.2

84.1

90

 

80

174

 

 

 

 

 

 

 

 

 

46.1/ 46.1

50/ 50**

49/ 49

281/281

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

73.2/

77.3

80/

80

74/

78

303/306

 

208/230-3-60

187

254

13.9

 

105

1.4

7.5

12.0/16.0

33.3/

38.5

87.7/

94.2

90/100

87/

93

314/319††

 

 

 

 

 

 

 

 

 

18.6/24.8

51.6/

59.7

110.6/120.7

125/125

108/118

332/341††

102

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

129.3/142.3

150/150

126/138

347/358††

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

156.5/173.6

175/175

151/166

369/383††

(81/2 Tons)

 

 

 

 

 

 

 

 

24.5

25**

26

145

 

 

 

 

 

 

 

 

 

13.9

16.7

45.3

50**

45

162

 

460-3-60

414

508

7.9

 

55.0

0.7

3.4

16.5

19.8

49.2

50**

49

165

 

 

 

 

 

 

 

 

 

27.8

33.4

66.2

70

 

64

179

 

 

 

 

 

 

 

 

 

33.0

39.7

74.1

80

 

72

185

 

 

 

 

 

 

 

 

 

41.7

50.2

87.2

90

 

84

196

 

 

 

 

 

 

 

 

 

61.6/ 61.6

70/ 70

65/ 65

341/341

 

 

 

 

 

 

 

 

 

7.8/10.4

21.7/

25.0

88.8/

92.9

90/100

90/

94

363/366††

 

208/230-3-60

187

254

19.3

 

123.0

1.4

10.6

12.0/16.0

33.3/

38.5

103.3/109.8

110/110

104/110

375/380††

 

 

 

 

 

 

 

 

 

24.0/32.0

66.6/

77.0

144.9/157.9

150/175

142/154

408/418††

120

 

 

 

 

 

 

 

 

31.8/42.4

88.3/102.0

172.0/189.1

175/200

167/183

430/443††

 

 

 

 

 

 

 

 

37.6/50.0

104.4/120.3

192.1/181.9

200/200

185/204

446/462††

(10 Tons)

 

 

 

 

 

 

 

 

30.9

35**

33

172

 

 

 

 

 

 

 

 

 

16.5

19.8

55.6

60**

55

191

 

460-3-60

414

508

10.0

 

62.0

0.7

4.8

27.8

33.4

72.6

80

71

205

 

 

 

 

 

 

 

 

 

33.0

39.7

80.5

90

78

211

 

 

 

 

 

 

 

 

 

41.7

50.2

93.6

100

90

222††

 

 

 

 

 

 

 

 

 

50.0

60.1

91.0

100

102

232††

549B, 549C

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor-Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor-Fan Motor

RLA

Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

†Heaters are field installed only. **Fuse or HACR circuit breaker.

††Electrical disconnect cannot be used if electric heater is installed.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

%Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

 

=

1371

 

 

3

 

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con- tact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

POWER EXHAUST

MCA

MCA

MCA

MOCP

(for separate

PART NO.

(230 v)

(460 v)

(575 v)

power source)

 

 

 

 

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

N/A — Not available

NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCP.

Check MCA and MOCP when power exhaust is powered through the unit. Deter- mine the new MCA including the power exhaust using the following formula: MCA New = MCA unit only + MCA of Power Exhaust

For example, using a 549B060 unit with MCA = 35.6 and MOCP = 40, with CRPWREXH030A01 power exhaust.

MCA New = 35.6 amps + 1.6 amps = 37.2 amps

If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP in this example is 40 amps and the MCA New is below 40; therefore the MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the power exhaust should be 15 amps per NEC.

122

Page 122
Image 122
Bryant 549C manual Nominal Voltage Compressor OFM Minimum Unit, IFM Electric Heat Power Supply Disconnect Voltage Range