TYPICAL WIRING SCHEMATICS — 549B, 549C (cont)

a48-7910

LEGEND

NOTE:

 

IAQ — Indoor Air Quality

Potentiometer Defaults Settings:

Power Exhaust

Middle

LA — Low Ambient Lockout Device

Minimum Pos.

Fully Closed

POT— Potentiometer

DCV Max.

Middle

OAT— Outdoor-Air Temperature

DCV Set

Middle

RAT — Return-Air Temperature

Enthalpy

C Setting

 

NOTES:

1.620 ohm, 1 watt 5% resister should be removed only when using differen- tial enthalpy or dry bulb.

2.If a separate field-supplied 24v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded.

3.For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position.

EconoMi$erIV Wiring — 549B036-120, 549C024-060

549B, 549C

500 OHM RESISTOR

NOTE 1

RUN

NOTE 2

-

+

50HJ540573

ACTUATOR

ASSEMBLY

OPTIONAL CO2

SENSOR 4 - 20 mA

OUTPUT

DIRECT DRIVE

ACTUATOR

 

BLACK

4

 

 

 

 

3

 

 

5

 

BLUE

2

 

 

 

 

8

VIOLET

 

6

 

 

PINK

 

7

 

 

 

RED

1

 

 

 

 

10

YELLOW

 

11

 

9

 

 

 

WHITE

12

 

 

a50-8053

ECONOMISER2 PLUG

 

NOTES:

1.Switch on actuator must be in run position for economizer to operate.

2.50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

EconoMi$er2 Wiring — 549B036-120, 549C024-060