GUIDE SPECIFICATIONS — 548F036-120 (cont)
f.EconoMi$erIV and EconoMi$er2 shall be equipped with a barometric relief damper capable of relieving up to 100% return air.
g.Designed to close damper(s) during
h.Dry bulb
i.The EconoMi$erIV and EconoMi$er2 shall have a
j.EconoMi$erIV microprocessor control shall pro- vide control of internal building pressure through its accessory power exhaust function. Factory set at 100%, with a range of 0% to 100%.
k.EconoMi$er2 shall be capable of control from a 4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control (required for third party control interface).
l.EconoMi$erIV Microprocessor Occupied Mini- mum Damper Position Setting maintains the minimum airflow into the building during occupied period providing design ventilation rate for full occupancy (damper position during heating). A remote potentiometer may be used to override the set point.
m.EconoMi$erIV Microprocessor Unoccupied Mini- mum Damper Position Setting — The EconoMi$erIV damper shall be completely closed when the unit is in the occupied mode.
n.EconoMi$erIV Microprocessor IAQ/DCV Maxi- mum Damper Position Setting — Setting the maximum position of the damper prevents the introduction of large amounts of hot or cold air into the space. This position is intended to satisfy the base minimum ventilation rate.
o.EconoMi$erIV Microprocessor IAQ/DCV control modulates the
p.Compressor lockout sensor (opens at 35 F, closes at 50 F).
q.Actuator shall be direct coupled to economizer gear, eliminating linkage arms and rods.
r.Control LEDs:
1)When the
2)The IAQ LED indicates when the module is on the DCV mode.
3)The EXH LED indicates when the exhaust fan contact is closed.
s. Remote Minimum Position Control — A field- installed accessory remote potentiometer shall allow the
3. 50% Manual
Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit up to 50% outdoor air for
4. 100% Manual
Manual damper package shall consist of damper birdscreen, and rainhood which can be preset to admit up to 100% outdoor air for
*5. 100%
a.
b.Damper shall close upon indoor fan shutoff.
c.Designed to close damper during loss of power situations.
d.Equipped with barometric relief damper.
*6. 25%
a.
b.Damper shall close upon indoor fan shutoff.
*7. Electric Resistance Heaters:
a.Open wire nichrome elements with all necessary safety operating controls.
b.UL listed and indicated on basic unit informative plate.
c.Available in multiples to match heating requirements.
d.Single point kits available for each heater when required.
*8. Head Pressure Control Packages:
Package shall consist of
* 9. Thermostat and Subbase:
Thermostat and subbase provide staged cooling and heating automatic (or manual) changeover, fan con- trol, and indicator light.
10.
Kit shall provide connectors to permit electrical con- nections to be brought to the unit through the basepan.
* 11. Electronic Programmable Thermostat:
Unit shall be capable of using deluxe
548F
71