PERFORMANCE DATA — 549B, 549C (cont)

ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060

UNIT

VOLTAGE

ACCESSORY

ACCESSORY HEATER

SINGLE POINT BOX

 

 

PART NUMBER

PACKAGE NO.

 

 

549B, 549C

(60 Hz)

 

kW

 

 

 

 

 

CRHEATER---A00

CRSINGLE---A00

 

 

 

 

 

 

 

 

 

024

208/230/240

3.3/

4.0/

4.4

001

 

 

4.9/

6.0/

6.5

002

 

 

(2 Tons)

(single phase)

6.5/

8.0/

8.7

003

004

 

 

 

 

7.9/

9.6/10.5

004

004

 

 

 

 

3.3/

4.0/

4.4

001

 

 

 

208/230/240

4.9/

6.0/

6.5

002

 

 

 

6.5/

8.0/

8.7

003

004

 

 

 

(single phase)

 

 

 

7.9/

9.6/10.5

004

004

 

 

 

 

 

 

 

 

9.8/12.0/13.0*

002 & 002

005

 

 

036

 

3.3/

4.0/

4.4

001

 

 

208/230/240

4.9/

6.0/

6.5

002

 

 

(3 Tons)

6.5/

8.0/

8.7

003

 

 

(3 phase)

 

 

 

7.9/

9.6/10.5

004

 

 

 

 

 

 

 

 

12.0/14.7/16.0

005

002

 

 

 

460/480

5.5/ 6.0

006

 

 

 

8.1/ 8.8

007

 

 

 

(3 phase)

10.6/11.5

008

 

 

 

 

12.9/14.0

009

 

 

 

 

3.3/

4.0/

4.4

001

 

 

 

208/230/240

6.5/

8.0/

8.7

003

004

 

 

 

9.8/12.0/13.0*

002 & 002

005

 

 

 

(single phase)

 

 

 

13.1/16.0/17.4*

003 & 003

005

 

 

 

 

 

 

 

 

15.8/19.3/21.0*

004 & 004

003

 

 

048

 

4.9/

6.0/

6.5

002

 

 

208/230/240

6.5/

8.0/

8.7

003

 

 

(4 Tons)

 

 

(3 phase)

12.0/14.7/16.0

005

002

 

 

 

 

15.8/19.3/21.0*

004 & 004

003

 

 

 

460/480

5.5/ 6.0

006

 

 

 

10.6/11.5

008

 

 

 

(3 phase)

12.9/14.0

009

 

 

 

 

21.1/23.0*

008 & 008

 

 

 

 

 

 

 

 

4.9/

6.0/

6.5

002

004

 

 

 

208/230/240

6.5/

8.0/

8.7

003

004

 

549B,

 

9.8/12.0/13.0*

002 & 002

005

 

 

(single phase)

 

 

13.1/16.0/17.4*

003 & 003

005

 

 

 

 

15.8/19.3/21.0*

004 & 004

005

 

549C

 

 

4.9/

6.0/

6.5

002

001

 

060

208/230/240

7.9/

9.6/10.5

004

002

 

12.0/14.7/16.0

005

002

 

 

(5 Tons)

(3 phase)

 

 

15.8/19.3/21.0*

004 & 004

003

 

 

 

 

19.9/24.3/26.5*

004 & 005

002

 

 

 

 

5.5/ 6.0

006

 

 

 

460/480

10.6/11.5

008

 

 

 

12.9/14.0

009

 

 

 

(3 phase)

 

 

 

21.1/23.0*

008 & 008

 

 

 

 

 

 

 

 

23.4/25.5*

008 & 009

 

 

 

 

4.9/

6.0/

6.5

002

 

 

 

208/230/240

7.9/

9.6/10.5

004

002

 

 

 

12.0/14.7/16.0

005

002

 

 

 

(3 phase)

 

 

 

15.8/19.3/21.0*

004 & 004

003

 

 

072

 

19.9/24.3/26.5*

004 & 006

003

 

 

(6 tons)

 

5.5/ 6.0

006

 

 

 

460/480

10.6/11.5

008

 

 

 

12.9/14.0

009

 

 

 

(3 phase)

 

 

 

21.1/23.0*

008 & 008

 

 

 

 

 

 

 

 

23.4/25.5*

008 & 009

 

 

*Two heater packages required to provide kW indicated.

NOTES:

1.The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.

2.To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kWnew = 16 kW (215/240)2

kWnew = 12.8 kW (rating at 215 v)

117

Page 117
Image 117
Bryant manual Electric Heating Capacities 549B036-120 and 549C024-060, 549B, 549C, CRHEATER---A00 CRSINGLE---A00, Tons