Bryant manual Multiplication Factors, Outdoor Sound Power Total Unit, 549B, 549C

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 118
Image 118
MULTIPLICATION FACTORS

549B, 549C

PERFORMANCE DATA — 549B, 549C (cont)

ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060 (cont)

 

 

 

 

ACCESSORY

ACCESSORY SINGLE

UNIT

VOLTAGE

ACCESSORY

HEATER

POINT BOX PART NO.

549B

(60 Hz)

 

kW

PART NUMBER

 

CRSINGLE---A00

 

 

 

 

CRHEATER---A00

 

 

 

 

 

 

 

7.8/

9.6/10.4

117

007

 

208/230/240

12.0/14.7/16.0

110

007

 

18.6/22.8/24.8

111

009

 

(3 phase)

 

24.0/29.4/32.0

112

009

 

 

090

 

31.8/39.0/42.4*

112,117

013

(71/2 Tons)

 

12.8/13.9

116

006

 

460/480

15.2/16.5

113

006

 

25.6/27.8

114

008

 

(3 phase)

 

30.4/33.0

115

008

 

 

 

 

38.4/41.7*

114,116

 

 

7.8/

9.6/10.4

117

012

 

208/230/240

12.0/14.7/16.0

110

012

 

18.6/22.8/24.8

111

015

 

(3 phase)

 

24.0/29.4/32.0

112

015

 

 

102

 

31.8/39.0/42.4*

112,117

017

(81/2 Tons)

 

12.8/13.9

116

011

 

460/480

15.2/16.5

113

011

 

25.6/27.8

114

014

 

(3 phase)

 

30.4/33.0

115

014

 

 

 

 

38.4/41.7*

114,116

016

 

 

7.8/

9.6/10.4

117

012

 

208/230/240

12.0/14.7/16.0

110

012

 

24.0/29.4/32.0

112

015

 

(3 phase)

 

31.8/39.0/42.4*

112,117

017

 

 

120

 

37.6/46.2/50.0*

112,110

017

(10 Tons)

 

15.2/16.5

113

011

 

460/480

25.6/27.8

114

014

 

30.4/33.0

115

014

 

(3 phase)

 

38.4/41.7*

114,116

016

 

 

 

 

46.0/50.0*

115,113

016

*Two heater packages required to provide kW indicated.

NOTES:

1.The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.

2.To determine heater kW at voltages other than those shown in table, use the following formula: Heater kWnew = Heater kW rated x (unit power distribution voltage/rated heater voltage)2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v kWnew = 16 kW (215/240)2

kWnew = 12.8 kW (rating at 215 v)

MULTIPLICATION FACTORS

HEATER RATING

 

 

 

 

ACTUAL HEATER VOLTAGE

 

 

 

 

VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

600

0.840

0.918

1.000

NOTE: The following equation converts kW of heat energy to Btuh:

EXAMPLE: 34 kW (at 230 v) heater on 208 v

kW x 3.413 = Btuh.

= 34.0 (.751 mult factor)

 

= 25.5 kW capacity at 208 v.

OUTDOOR SOUND POWER (TOTAL UNIT)

549B,

ARI

 

 

OCTAVE BANDS; Lw (A)

 

 

RATING

 

 

 

 

 

 

 

 

 

549C

63

125

250

500

1000

2000

 

4000

8000

(decibels)

 

024,036,048

76

50.8

63.4

62.2

65.9

69.2

65.9

 

63.0

56.5

060,072

80

57.6

70.2

66.9

71.7

74.7

72.2

 

67.8

62.4

090

82

62.3

69.3

71.5

74.7

76.2

72.9

 

68.7

61.5

102

84

64.6

71.1

73.3

76.9

77.6

73.7

 

70.6

63.7

120

84

64.6

71.1

73.3

76.9

77.6

73.7

 

70.6

63.7

ARI — Air Conditioning and Refrigeration Institute

Lw (A)— Unit A — Weighted Sound Power Level

118

Page 118
Image 118
Bryant manual Multiplication Factors, Outdoor Sound Power Total Unit, PERFORMANCE DATA — 549B, 549C cont