Bryant 549C manual CONTROLS cont, SEQUENCE OF OPERATION — 542J150,180

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 164
Image 164

CONTROLS (cont)

Continuous Air Circulation — Turn unit power on. Set system control at OFF position. Set fan switch at ON position. The indoor-fan contactor is energized through the thermostat switch and the indoor fan runs continuously.

Cycle-LOC™ Protection — If unit operation is interrupted by an open high-pressure switch, low-pressure switch, indoor coil freezestat, or by compressor internal line-break device (over- current or overtemperature), and compressor is calling for either cooling or heating, Cycle-LOC protection device simulta- neously locks out unit and lights a warning light on the thermo- stat. Restart the unit by manually turning thermostat to OFF and then to ON position. If any of the protective devices opens again, the unit continues to lock out until corrective action is taken.

NOTE: If the unit fails to operate due to compressor overcurrent condition, restart by manually resetting circuit breakers at the unit. Restart cannot be accomplished at the room thermostat.

Emergency Heat — If compressor is inoperative due to a tripped safety device (high or low pressure, indoor coil freez- estat, overcurrent, or overtemperature), the Cycle-LOC device locks out the compressor and lights a warning light on the room thermostat. When the switch is on (thermostat is set to the EM HT position), compressor circuit and outdoor thermostats are bypassed, and the second stage of thermostat energizes the indoor blower and the electric resistance heaters.

SEQUENCE OF OPERATION — 542J150,180

Cooling, Units Without Economizer — With unit main power on, set thermostat to COOL position and desired room tempera- ture. Set fan switch at AUTO. (on demand) or ON (continuous) position.

On a rise in room temperature, cooling contactor no. 1 in the thermostat closes. The indoor and outdoor fan motors start. If the 5-minute compressor time-delay (CTD) on the defrost board (DB) is satisfied, then compressor no. 1 (542J180) or unloaded compressor (542J150) contactor is energized and compressor will start. Compressor cycles on demand of the thermostat to satisfy room conditions. Each time the cooling contactor no. 1 opens, the CTD starts the 5-minute delay.

On 542J180 units, with an additional rise in room temperature, cooling contactor no. 2 in the thermostat closes, energizing compressor contactor no. 2. Compressor no. 2 starts and cycles on demand of the thermostat to satisfy the occupied space demands.

On 542J150 units, compressor runs fully loaded on a call for second-stage cooling.

Cooling, Units With Economizer — Upon a call for cooling, when outdoor ambient temperature is above the temperature control setting, the indoor and outdoor fans and compressor(s) energize. The economizer damper moves to vent position.

Upon a first-stage call for cooling, when outdoor ambient tem- perature is below the temperature control setting, the indoor fan starts and economizer damper modulates to maintain mixed-air temperature. The compressor(s) remains off.

Upon a second-stage call for cooling, compressor no. 1 (542J180) or loaded compressor (542J150) is energized and mechanical cooling is integrated with economizer cooling. Com- pressor no. 2 (542J180) is locked out. If the air temperature is

below 50 F, a cooling lockout switch prevents the compressor(s) from running.

When supply-air temperature drops below a fixed set point, the economizer damper modulates to maintain the temperature at the fixed set point.

A freeze protection thermostat (FPT) is located on the indoor coil. It detects frost build-up and turns off the compressor(s), allowing the coil to clear. Once frost has melted, the compres- sor can be reenergized.

Heating, Units Without Economizer — With unit main power on, set thermostat at HEAT position and desired room tempera- ture. Set fan switch at AUTO. (on demand) or ON (continuous) position.

On a drop in room temperature, heating contactor no. 1 in the thermostat closes, energizing heat relay (HR), reversing valve relay (RVR), reversing valve solenoids (RVS1 and RVS2) and compressor no. 2 contactor. Compressor (size 150) or com- pressor no. 2 (size 180) and indoor and outdoor fan motors start. If the 5-minute CTD on the DB is satisfied, then compres- sor no. 1 contactor is energized and compressor no. 1 will start.

On units equipped with electric heat, when additional heat is needed, heating contactor no. 2 in the thermostat closes, ener- gizing W2.

Heating, Units With Economizer — With unit main power on, set thermostat at HEAT position and desired room temperature. Set fan switch at AUTO. (on demand) or ON (continuous) posi- tion.

On a drop in room temperature, heating contactor no. 1 in the thermostat closes, energizing heat relay (HR), reversing valve relay (RVR), reversing valve solenoids (RVS1 and RVS2) and compressor no. 2 contactor. Compressor no. 2 (size 180) and indoor and outdoor fan motors start. If the 5-minute CTD on the DB is satisfied, then compressor (542J150) or compressor no. 1

(180)contactor is energized and compressor (542J150) or compressor no. 1 (180) will start. The outdoor-air damper stays at vent position while the indoor fan is operating.

On units equipped with electric heat, when additional heat is needed, heating contactor no. 2 in the thermostat closes, ener- gizing W2.

Defrost Cycle — When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT1 or DFT2), the defrost timer starts. At the end of a timed period (field set at 30, 50, or 90 minutes), the defrost cycle will begin. The defrost board energizes terminals O and W2, energizes the defrost relay (DR), deenergizes the reversing valve solenoids (RVS1 and RVS2), and energizes the electric heat. The outdoor-fan motor will stop.

The unit continues to defrost either until the coil temperature as measured by DFT1 or DFT2 reaches 65 F, or until unit com- pletes a 10-minute defrost cycle.

During the defrost mode, when a circuit defrosts, RVS will oscil- late between heating and cooling modes until defrost mode is complete. This will prevent the head pressure from getting too high.

At the end of the defrost cycle, the electric heaters (if applica- ble) will be deenergized, the reversing valve solenoids will be energized, and the outdoor fans will start.

164

Page 164
Image 164
Bryant 549C manual CONTROLS cont, SEQUENCE OF OPERATION — 542J150,180