PERFORMANCE DATA — 542J (cont)

GLYCOL COIL DATA* — 542J150,180

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

4400

 

 

 

 

5000

 

 

 

 

6200

 

 

EDB

EGT

 

 

 

 

 

 

 

 

% Glycol

 

 

 

 

 

 

 

 

 

 

 

25

 

 

50

 

 

25

 

 

50

 

 

25

 

 

50

 

 

 

Cap.

Gpm

Ldb

Cap.

Gpm

Ldb

Cap.

Gpm

Ldb

Cap.

Gpm

Ldb

Cap.

Gpm

Ldb

Cap.

Gpm

Ldb

55

200

310

33

120

293

33

116

333

35

117

315

36

113

375

40

111

353

40

108

180

255

27

108

237

27

105

274

29

106

254

29

102

308

33

101

285

33

98

 

160

200

21

97

181

21

93

215

23

95

194

22

91

241

25

91

217

25

87

70

200

274

29

127

257

29

124

294

31

124

276

31

121

331

35

119

310

35

116

180

218

23

116

201

23

112

235

25

114

216

25

110

264

28

109

241

28

106

 

160

164

17

104

146

17

100

176

19

103

156

18

99

197

21

99

174

20

96

80

200

249

26

132

233

27

129

268

28

130

250

28

126

301

32

125

280

32

122

180

194

21

121

177

20

117

209

22

119

190

22

115

234

25

115

212

24

112

 

160

140

15

109

123

14

106

150

16

108

131

15

104

168

18

105

146

17

102

 

 

LEGEND

Cap. —

Btuh x 1000

EDB

Entering Dry-Bulb Temperature (F)

EGT

Entering Glycol Temperature (F)

Gpm —

Gallons per Minute

Ldb

Leaving Dry-Bulb Temperature (F)

*This accessory glycol coil is intended for use with a MINIMUM of 25% glycol solution. It IS NOT intended for use solely with water due to freeze-up conditions and the resulting water damage to the condi- tioned space.

NOTE: Fluid Δt = 20 F.

GLYCOL COIL RATINGS — 542J150,180

ENTERING

 

 

 

 

 

 

CFM

 

 

 

 

 

FLUID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

 

5000

 

 

6000

 

8000

TEMP

 

 

 

 

 

(F)

GPM

 

ΔP

GPM

 

ΔP

 

GPM

 

ΔP

GPM

 

ΔP

200

27

 

1.2

31

 

1.5

 

35

 

1.8

41

 

2.4

180

22

 

0.9

25

 

1.1

 

27

 

1.3

32

 

1.6

160

16

 

0.6

19

 

0.7

 

20

 

0.8

24

 

1.0

NOTE: ΔP is the fluid pressure in ft of head.

MULTIPLICATION FACTORS

HEATER RATING

 

 

 

 

ACTUAL HEATER VOLTAGE

 

 

 

 

VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

600

0.840

0.918

1.000

NOTE: The following equation converts kW of heat energy to Btuh:

EXAMPLE: 34 kW (at 230 v) heater on 208 v

kW x 3.413 = Btuh.

= 34.0 (.751 mult factor)

 

= 25.5 kW capacity at 208 v.

542J

152

Page 152
Image 152
Bryant 549C manual Glycol Coil DATA* 542J150,180, Glycol Coil Ratings 542J150,180