Bryant 549C manual PERFORMANCE DATA - 548F, Cooling Capacities

Models: 549C

1 170
Download 170 pages 54.16 Kb
Page 21
Image 21
PERFORMANCE DATA — 548F

 

 

 

 

 

 

 

 

 

PERFORMANCE DATA — 548F

 

 

 

 

 

 

 

 

 

 

 

 

COOLING CAPACITIES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

548F036 (3 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

Outdoor

 

 

900/0.10

 

 

 

1200/0.15

 

 

 

1500/0.21

 

Entering Air

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

62

 

72

 

67

62

 

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

42.4

 

39.9

36.5

 

43.0

 

41.2

38.7

 

45.1

 

42.8

 

40.3

 

SHC

 

16.7

 

22.0

26.8

 

17.5

 

24.2

30.9

 

19.3

 

26.9

 

34.1

 

 

kW

 

2.77

 

2.71

2.62

 

2.78

 

2.74

2.68

 

2.85

 

2.79

 

2.73

85

 

TC

 

41.5

 

38.4

34.8

 

43.3

 

40.4

37.0

 

44.0

 

41.7

 

38.7

 

SHC

 

16.6

 

21.6

26.2

 

18.2

 

24.6

30.3

 

19.3

 

27.2

 

33.7

 

 

kW

 

3.01

 

2.92

2.80

 

3.07

 

2.98

2.88

 

3.09

 

3.03

 

2.94

95

 

TC

 

40.0

 

36.3

33.0

 

42.3

 

38.5

35.2

 

43.4

 

40.0

 

36.7

 

SHC

 

16.2

 

20.9

25.7

 

18.2

 

24.2

29.8

 

19.7

 

27.2

 

32.7

 

 

kW

 

3.24

 

3.10

2.99

 

3.32

 

3.19

3.07

 

3.36

 

3.24

 

3.13

105

 

TC

 

38.4

 

34.7

31.0

 

40.0

 

36.7

33.1

 

41.2

 

37.7

 

35.2

 

SHC

 

15.7

 

20.5

24.8

 

17.5

 

23.9

28.8

 

19.3

 

26.6

 

31.7

 

 

kW

 

3.47

 

3.32

3.16

 

3.53

 

3.41

3.26

 

3.58

 

3.44

 

3.35

115

 

TC

 

36.1

 

32.5

28.9

 

38.1

 

34.3

31.1

 

39.3

 

35.5

 

33.2

 

SHC

 

15.1

 

19.8

23.9

 

17.2

 

23.2

27.8

 

19.1

 

26.2

 

30.2

 

 

kW

 

3.66

 

3.50

3.32

 

3.76

 

3.59

3.44

 

3.81

 

3.65

 

3.54

125

 

TC

 

34.2

 

30.5

26.8

 

35.9

 

32.0

29.3

 

36.8

 

33.0

 

31.3

 

SHC

 

14.6

 

19.2

22.9

 

16.7

 

22.6

26.3

 

18.5

 

25.5

 

28.4

 

 

kW

 

3.88

 

3.68

3.49

 

3.97

 

3.77

3.62

 

4.02

 

3.83

 

3.74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

548F048 (4 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

Outdoor

 

 

1200/0.11

 

 

 

1600/0.15

 

 

 

2000/0.22

 

Entering Air

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

62

 

72

 

67

62

 

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

55.5

 

51.9

47.4

 

56.9

 

54.6

50.3

 

59.3

 

56.5

 

52.1

 

SHC

 

24.5

 

31.2

37.4

 

26.0

 

35.2

43.4

 

28.4

 

39.0

 

47.6

 

 

kW

 

3.80

 

3.70

3.55

 

3.84

 

3.79

3.66

 

3.93

 

3.86

 

3.71

85

 

TC

 

53.4

 

49.7

45.3

 

56.3

 

52.6

47.8

 

57.5

 

54.1

 

49.8

 

SHC

 

23.8

 

30.4

36.7

 

26.3

 

34.9

42.6

 

28.3

 

38.6

 

46.9

 

 

kW

 

4.10

 

3.99

3.84

 

4.23

 

4.11

3.94

 

4.27

 

4.16

 

4.01

95

 

TC

 

52.0

 

47.4

43.0

 

53.7

 

49.9

45.5

 

54.5

 

51.6

 

47.4

 

SHC

 

23.4

 

29.6

35.8

 

25.5

 

33.9

41.6

 

27.3

 

38.2

 

45.2

 

 

kW

 

4.47

 

4.28

4.11

 

4.53

 

4.39

4.23

 

4.56

 

4.48

 

4.29

105

 

TC

 

49.3

 

45.0

40.6

 

51.8

 

47.2

43.0

 

52.6

 

48.7

 

45.4

 

SHC

 

22.5

 

28.8

34.7

 

25.3

 

33.0

40.3

 

27.1

 

37.1

 

43.3

 

 

kW

 

4.77

 

4.59

4.39

 

4.90

 

4.68

4.52

 

4.92

 

4.76

 

4.63

115

 

TC

 

46.6

 

42.4

38.0

 

48.8

 

44.6

40.6

 

50.2

 

45.8

 

43.2

 

SHC

 

21.7

 

27.9

33.6

 

24.3

 

32.4

38.7

 

26.8

 

36.1

 

41.2

 

 

kW

 

5.08

 

4.90

4.66

 

5.21

 

5.01

4.81

 

5.29

 

5.06

 

4.96

125

 

TC

 

44.0

 

39.6

35.4

 

45.6

 

41.6

38.3

 

47.0

 

42.9

 

40.9

 

SHC

 

20.9

 

26.9

32.4

 

23.3

 

31.6

36.5

 

25.9

 

35.6

 

39.0

 

 

kW

 

5.45

 

5.21

4.96

 

5.51

 

5.34

5.14

 

5.60

 

5.41

 

5.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

548F060 (5 TONS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

Indoor Entering Air — Cfm/BF

 

 

 

 

 

Outdoor

 

 

1500/0.05

 

 

 

2000/0.08

 

 

 

2500/0.14

 

Entering Air

 

 

 

 

 

Indoor Entering Air — Ewb (F)

 

 

 

 

 

 

(Edb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

67

62

 

72

 

67

62

 

72

 

67

 

62

 

 

 

 

 

 

 

 

 

 

75

 

TC

 

69.3

 

64.5

59.3

 

70.8

 

67.9

62.8

 

72.9

 

69.3

 

65.4

 

SHC

 

30.9

 

39.2

47.4

 

33.1

 

44.9

55.4

 

35.8

 

49.4

 

61.4

 

 

kW

 

4.28

 

4.15

4.03

 

4.32

 

4.25

4.12

 

4.38

 

4.29

 

4.19

85

 

TC

 

67.7

 

62.4

56.8

 

69.1

 

65.7

60.2

 

71.1

 

67.7

 

63.2

 

SHC

 

30.4

 

38.6

46.5

 

32.8

 

44.6

54.4

 

35.8

 

50.0

 

59.8

 

 

kW

 

4.76

 

4.61

4.49

 

4.79

 

4.72

4.56

 

4.86

 

4.78

 

4.65

95

 

TC

 

65.2

 

59.8

54.4

 

67.7

 

62.9

57.6

 

69.1

 

64.8

 

60.7

 

SHC

 

29.6

 

37.6

45.5

 

32.8

 

43.6

53.2

 

35.6

 

49.3

 

57.7

 

 

kW

 

5.27

 

5.10

4.97

 

5.35

 

5.20

5.07

 

5.39

 

5.27

 

5.14

105

 

TC

 

62.3

 

57.2

51.8

 

65.1

 

59.6

54.9

 

66.8

 

61.7

 

58.3

 

SHC

 

28.6

 

33.8

44.4

 

32.1

 

42.6

51.6

 

35.4

 

48.2

 

55.5

 

 

kW

 

5.79

 

5.66

5.50

 

5.90

 

5.73

5.61

 

5.97

 

5.79

 

5.68

115

 

TC

 

59.7

 

54.2

49.0

 

61.7

 

57.0

52.5

 

63.2

 

58.4

 

55.8

 

SHC

 

27.6

 

35.8

43.2

 

31.1

 

41.9

49.6

 

34.3

 

47.0

 

53.2

 

 

kW

 

6.37

 

6.24

6.06

 

6.47

 

6.34

6.20

 

6.53

 

6.36

 

6.31

125

 

TC

 

56.5

 

51.0

46.0

 

58.2

 

53.5

49.8

 

59.4

 

55.1

 

53.0

 

SHC

 

26.8

 

34.7

41.9

 

30.0

 

40.8

47.3

 

33.0

 

46.5

 

50.5

 

 

kW

 

7.03

 

6.87

6.65

 

7.07

 

6.96

6.82

 

7.13

 

7.03

 

6.96

LEGEND

BF — Bypass Factor

Edb — Entering Dry-Bulb

Ewb — Entering Wet-Bulb

kW — Compressor Motor Power Input

Ldb — Leaving Dry-Bulb

Lwb — Leaving Wet-Bulb

SHC — Sensible Heat Capacity

(1000 Btuh) Gross

TC — Total Capacity (1000 Btuh) Gross

NOTES:

1.Direct interpolation is permissible. Do not extrapolate.

2.The following formulas may be used:

tldb = tedb

sensible capacity (Btuh)

 

1.10 x cfm

tlwb = Wet-bulb temperature corre- sponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: hewb = Enthalpy of air enter- ing evaporator coil

3.The SHC is based on 80 F edb tem- perature of air entering indoor coil. Below 80 F edb, subtract (corr factor

x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

548F

21

Page 21
Image 21
Bryant 549C manual PERFORMANCE DATA - 548F, Cooling Capacities, Above 80 F edb, add corr factor x cfm to SHC