• Press EXIT toreturn to the previous screen level.
• Press INCREASE or DECREASE tochange the high-
lighted point value.
TO VIEWPOINT STATUS (Fig. 15) — Point Status is the
actualvalue of all of the temperatures, pressures, relays, and
actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS to view the list of
Point Status tables.
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• Status01 — Status of control points and sensors
• Status02 — Status of relays and contacts
Status03 — Status of both optional 8-input modules and
sensors
3. Press SELECT to view the Point Status table desired.
4. On the Point Status table press NEXT or
PREVIOUS untildesired point is displayed on the screen.
OVERRIDE OPERATIONS
To Override aValue or Status
1. On the Point Status table press NEXT or
PREVIOUS to highlight the desired point.
2. Press SELECT to select the highlighted point. Then:
For Discrete Points — Press START or STOP tose-
lect the desired state.
For Analog Points — Press INCREASE or
DECREASE to select the desired value.
3. Press ENTER to register new value.
NOTE: When overriding or changing metric values, it is
necessary to hold the softkey down for a few seconds in or-
der to see a value change, especially on kilopascal
values.
To Remove an Override
1. On the Point Status table press NEXT or
PREVIOUS to highlight the desired point.
2. Press SELECT to access the highlighted point.
Fig. 15 − Example of Point Status Screen
(Status01)
15