6. Be sure that fused disconnects or circuit breakers have
been supplied for the oil pump, power panel, and
pumpout unit.
7. Checkthat all electrical equipment and controls are prop-
erly grounded in accordance with job drawings, certi-
fied drawings, and all applicable electrical codes.
8. Make sure that the customer’s contractor has verified
proper operation of the pumps, cooling tower fans, and
associated auxiliary equipment. This includes ensuring
thatmotors are properly lubricated and have proper elec-
trical supply and proper rotation.
9. Forfield-installed starters only, test the chiller compres-
sor motor and its power lead insulation resistance with
a 500-v insulation tester such as a megohmmeter.(Use
a 5000-v tester for motors rated over 600 v.) Factory-
mounted starters do not require a megohm test.
a. Open the starter main disconnect switch and follow
lockout/tagout rules.
If the motor starter is a solid-state starter, the
motor leads must be disconnected from the starter
beforean insulation test is performed. The voltage
generated from the tester can damage the starter
solid-state components.
b. With the tester connected to the motor leads, take
10-second and 60-second megohm readings as
follows:
6-LeadMotor — Tie all 6 leads together and test be-
tween the lead group and ground. Next tie leads in
pairs, 1 and 4, 2 and 5, and 3 and 6. Test between
each pair while grounding the third pair.
3-Lead Motor — Tie terminals 1, 2, and 3 together
and test between the group and ground.
c. Divide the 60-second resistance reading by the
10-second reading. The ratio, or polarization index,
must be one or higher. Both the 10- and 60-second
readings must be at least 50 megohms.
If the readings on a field-installed starter are unsat-
isfactory,repeat the test at the motor with the power
leads disconnected. Satisfactory readings in this sec-
ond test indicate the fault is in the power leads.
NOTE:Unit-mounted starters do not have to be meg-
ohm tested.
10. Tighten up all wiring connections to the plugs on the
SMM, 8-input, and PSIO modules.
11. Ensure that the voltage selector switch inside the power
panel is switched to the incoming voltage rating.
12. Onchillers with free-standing starters, inspect the power
panelto ensure that the contractor has fed the wires into
thebottom of the panel. Wiring into the top of the panel
can cause debris to fall into the contactors. Clean and
inspect the contactors if this has occurred.
CarrierComfort Network Interface — TheCarrier
Comfort Network (CCN) communication bus wiring is sup-
plied and installed by the electrical contractor.It consists of
shielded, 3-conductor cable with drain wire.
Thesystem elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
the positive pins of the system element on either side of it;
thenegative pins must be wired to the negative pins; the sig-
nal ground pins must be wired to signal ground pins.
To attach the CCN communication bus wiring, refer to
the certified drawings and wiring diagrams. The wire is in-
sertedinto the CCN communications plug (COMM1) on the
PSIO module. This plug also is referred to as J5.
NOTE: Conductors and drain wire must be 20 AWG
(American Wire Gage) minimum stranded, tinned copper.
Individual conductors must be insulated with PVC, PVC/
nylon,vinyl, Teflon, or polyethylene. An aluminum/polyester
100% foil shield and an outer jacket of PVC, PVC/nylon,
chrome vinyl or Teflonwith a minimum operating tempera-
ture range of –20 C to 60 C is required. See table below for
cables that meet the requirements.
MANUFACTURER CABLE NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
When connecting the CCN communication bus to a sys-
tem element, a color code system for the entire network is
recommendedto simplify installation and checkout. The fol-
lowing color code is recommended:
SIGNAL
TYPE CCN BUS CONDUCTOR
INSULATIONCOLOR
PSIO MODULE
COMM 1 PLUG (J5)
PIN NO.
+RED 1
Ground WHITE 2
BLACK 3
Check Starter
BE AWARE that certain automatic start arrangements
can engage the starter. Open the disconnect ahead of
thestarter in addition to shutting off the chiller or pump.
Use the instruction and service manual supplied by the
starter manufacturer to verify that the starter has been in-
stalled correctly.
The main disconnect on the starter front panel may not
deenergizeall internal circuits. Open all internal and re-
mote disconnects before servicing the starter.
Whenevera starter safety trip device activates, wait at least
30 seconds before resetting the safety. The microprocessor
maintains its output to the 1CR relay for 10 seconds to de-
termine the fault mode of failure.
MECHANICAL-TYPE STARTERS
1. Check all field wiring connections for tightness, clear-
ance from moving parts, and correct connection.
2. Checkthe contactor(s) to be sure they move freely. Check
themechanical interlock between contactors to ensure that
1S and 2M contactors cannot be closed at the same time.
Check all other electro-mechanical devices, e.g., relays,
timers, for free movement. If the devices do not move
freely, contact the starter manufacturer for replacement
components.
48