Table 9 Ð LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

F. START-UP FAILURES: This is an alarm condition. A manual reset is required to clear.

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

FAILURE TO START

 

OILPD [VALUE] exceeded limit of

Check for closed oil supply valves. Check

LOW OIL PRESSURE

oil ®lter. Check for low oil temperature.

[LIMIT]*. Check oil pump system.

 

 

Check transducer accuracy.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for excessive refrigerant in oil sump.

FAILURE TO START

 

OILPD [VALUE] exceeded limit of

Run oil pump manually for 5 minutes.

OIL PRESS SENSOR FAULT

Check transducer calibration. Check cooler

[LIMIT]*. Check oil pressure sensor.

 

 

pressure transducer calibration. Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wiring. Replace transducer if necessary.

FAILURE TO START

LOW CHILLED WATER

EVFL Evap Flow Fault: Check water

Check wiring to ¯ow switch. Check through

FLOW

pump/¯ow switch.

Control Test for proper switch operation.

 

FAILURE TO START

LOW CONDENSER

CDFL Cond. Flow Fault: Check water

Check wiring to ¯ow switch. Check through

WATER FLOW

pump/¯ow switch.

Control Test for proper switch operation.

 

FAILURE TO START

STARTER FAULT

STR

 

 

 

FLT Starter Fault: Check Starter

A starter protective device has faulted.

 

 

 

Check starter for ground fault, voltage trip,

for Fault Source.

 

 

temperature trip, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

FAILURE TO START

STARTER OVERLOAD TRIP

STR

 

 

 

FLT Starter Overload Trip:

Reset overloads before restart.

Check amps calibration/reset overload.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check voltage supply. Check transformers

FAILURE TO START

LINE VOLTAGE DROPOUT

V

 

 

 

P Single-Cycle Dropout Detected:

for supply. Check with utility if voltage

 

 

 

supply is erratic. Monitor must be installed

Check voltage supply.

 

 

to con®rm consistent, single-cycle drop-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outs. Check low oil pressure switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the high-pressure switch. Check for

 

 

High Condenser Pressure [OPEN]*:

proper condenser pressures and con-

 

 

denser water¯ow. Check for fouled tubes.

 

 

Check switch, oil pressure contact, and

 

 

Check the 2C aux contact and the oil

 

 

water temperature/¯ow.

 

HIGH CONDENSER

pressure switch in the power panel. This

FAILURE TO START

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

alarm is not caused by the transducer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Condenser Pressure [VALUE]*:

Check water ¯ow in condenser. Check for

 

 

fouled tubes. Transducer should be

 

 

Check switch, water ¯ow, and

 

 

checked for accuracy. This alarm is not

 

 

transducer.

 

 

caused by the high pressure switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

FAILURE TO START

EXCESS ACCELERATION

CA

 

 

 

 

 

 

P Excess Acceleration:

Check that guide vanes are closed at

 

 

 

 

start-up. Check starter for proper operation.

TIME

Check guide vane closure at start-up.

 

Reduce unit pressure if possible.

 

 

 

 

 

 

 

 

 

 

 

 

 

FAILURE TO START

STARTER TRANSITION

RUN

 

 

 

AUX Starter Transition Fault:

Check starter for proper operation.

FAULT

Check 1CR/1M/Interlock mechanism.

Run contact failed to close.

 

FAILURE TO START

1CR AUX CONTACT FAULT

1CR

 

 

AUX Starter Contact Fault:

Check starter for proper operation.

Check 1CR/1M aux. contacts.

Start contact failed to close.

 

 

 

 

CA

 

 

 

 

 

P Motor Amps Not Sensed:

Check for proper motor amps signal to

FAILURE TO START

MOTOR AMPS NOT SENSED

 

SMM. Check wiring from SMM to current

 

 

 

Check motor load signal.

transformer. Check main motor circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker for trip.

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressures at transducers indicate another

FAILURE TO START

CHECK REFRIGERANT

Current Refrigerant Properties

refrigerant type in Control Test. Make sure

Abnormal Ð

to access the ATTACH TO NETWORK

TYPE

 

Check Selection of refrigerant type

DEVICE table after changing refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

type.

 

 

 

 

 

 

 

 

 

 

 

 

 

The oil pressure differential switch is open

 

 

Low Oil Pressure [LIMIT]*:

when the compressor tried to START.

FAILURE TO START

 

Check the switch for proper operation.

LOW OIL PRESSURE

Check oil pressure switch/pump

Also, check the oil pump interlock (2C aux)

 

 

and 2C aux.

 

 

in the power panel and the high condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. [OPEN] indicates that an input circuit is open.

NOTE: See Legend on page 68.

70

Page 70
Image 70
Carrier 19XL specifications LOW Chilled Water

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.