3.Some dashpot-type magnetic overload relays must be filled with oil on the jobsite. If the starter is equipped with de- vices of this type, remove the ¯uid cups from these mag- netic overload relays. Add dashpot oil to cups per instructions supplied with the starter. The oil is usually shipped in a small container attached to the starter frame near the re- lays. Use only dashpot oil supplied with the starter. Do not substitute.

Factory-®lled dashpot overload relays need no oil at start-up and solid-state overload relays do not have oil.

4.Reapply starter control power (not main chiller power) to check electrical functions. When using a reduced-voltage starter (such as a wye-delta type) check the transition timer for proper setting. The factory setting is 30 seconds (± 5 seconds), timed closing. The timer is adjustable in a range between 0 and 60 seconds and settings other than the nominal 30 seconds may be chosen as needed (typi- cally 20 to 30 seconds are used).

When the timer has been set, check that the starter (with relay 1CR closed) goes through a complete and proper start cycle.

BENSHAW, INC. SOLID-STATE STARTER

This equipment is at line voltage when AC power is connected. Pressing the STOP button does not remove voltage. Use caution when adjusting the potentiometers on the equipment.

1.Check that all wiring connections are properly termi- nated to the starter.

2.Verify that the ground wire to the starter is installed prop- erly and is of sufficient size.

3.Verify that the motors are properly grounded to the starter.

4.Check that all of the relays are properly seated in their sockets.

5.Verify that the proper ac input voltage is brought into the starter per the certi®ed drawings.

6.Verify the initial factory settings of the starting torque and ramp potentiometers are set per the note on the schematic for the starters.

NOTE: The potentiometers are located at the lower left hand corner on the circuit board mounted in front of the starter power stack (Fig. 30 and 31).

The starting torque potentiometer should be set so that when the PIC calls for the motor to start, the rotor should just start to turn. The nominal dial position for a 60 Hz motor is approximately the 11:30 position. The nominal dial position for a 50 Hz motor is approximately in the 9:30 position because the board is turned on its side, so that the 9:00 o'clock position is located where the 6:00 o'clock position would normally be located. The ramp potentiometer should be set so that the motor is up to full speed in 15 to 20 seconds, the bypass contactors have energized, and the auxiliary LCD is energized.

7.Proceed to apply power to the starter.

8.The Power +15 and Phase Correct LEDs should be on. If not, see the starter Troubleshooting Guide section.

LEGEND

1Ð Phase Voltage Indicator

2Ð Starter Fault and Run LEDs (5)

·Overtemp

·Ground Fault

·Current Unbalance (CUB) While Stopped

·Current Unbalance

·Run (Start Initiated)

3Ð Starting Torque Potentiometer

4Ð Ramp Up Potentiometer

5Ð Phase Correct LED

6Ð Relay On LED

7Ð Power +15 and Auxiliary (Starter in RUN State) LEDs (Hidden)

8Ð SCR Indicator LEDs (Hidden)

9Ð Reset Button

Fig. 30 Ð Benshaw, Inc. Solid-State Starter

Power Stack

NOTE: Adjustments:

Starting torque Ð 0% to 100% rated motor torque. Ramp time to full motor voltage Ð 0.5 seconds to 60 seconds.

Fig. 31 Ð Ramp Up and Starting Torque

Potentiometers

49

Page 49
Image 49
Carrier 19XL specifications BENSHAW, INC. SOLID-STATE Starter, Benshaw, Inc. Solid-State Starter Power Stack

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.