Table 2 — LID Screens (cont)
EXAMPLE 5 — CONFIGURATION(CONFIG) DISPLAY SCREEN
Toaccess this display from the LID default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight CONFIG.
6. Press SELECT .
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULTVALUE
RESET TYPE 1
Degrees Reset at 20 mA –30-30 (–17-17) DEG F (DEG C) deg 20ma 10D(6D)
RESET TYPE 2
Remote Temp(No Reset) –40-245(–40-118) DEGF (DEG C) res rt1 85 (29)
Remote Temp(Full Reset) –40-245 (–40-118) DEG F (DEG C) res rt2 65(18)
Degrees Reset –30-30 (–17-17) DEG F (DEG C) res rt 10D(6D)
RESET TYPE 3
CHW Delta T (No Reset) 0-15 (0-8) DEG F (DEG C) restd 1 10D(6D)
CHW Delta T (Full Reset) 0-15 (0-8) DEGF (DEG C) restd 2 0D(0D)
Degrees Reset –30-30 (–17-17) DEG F (DEG C) deg chw 5D(3D)
Select/Enable Reset Type 0-3 res sel 0
ECW CONTROL OPTION DISABLE/ENABLE ecw opt DISABLE
Demand LimitAt 20 mA 40-100 % dem 20ma 40
20 mADemand Limit Option DISABLE/ENABLE dem sel DISABLE
Auto Restart Option DISABLE/ENABLE astart DISABLE
Remote Contacts Option DISABLE/ENABLE r contact DISABLE
TempPulldown Deg/Min 2-10 tmp ramp 3
Load Pulldown %/Min 5-20 kw ramp 10
Select Ramp Type: 0/1 ramp opt 1
Temp=0,Load=1
Loadshed Group Number 0-99 ldsgrp 0
Loadshed Demand Delta 0-60 % ldsdelta 20
Maximum Loadshed Time 0-120 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number 3-99 occpcxxe 3
Broadcast Option DISABLE/ENABLE occbrcst DISABLE
ICE BUILD Option DISABLE/ENABLE ibopt DISABLE
ICE BUILD TERMINATION
0 =Temp,1 =Contacts, 2 =Both 0-2 ibterm 0
ICE BUILD Recycle Option DISABLE/ENABLE ibrecyc DISABLE
NOTE: D= delta degrees.
EXAMPLE 6 — LEAD/LAG CONFIGURATIONDISPLAY SCREEN
Toaccess this display from the LID default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight Lead/Lag.
6. Press SELECT .LEAD/LAG CONFIGURATION SCREEN
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY=3 0-3 leadlag 0
Load Balance Option DISABLE/ENABLE loadbal DISABLE
Common Sensor Option DISABLE/ENABLE commsens DISABLE
LAG Percent Capacity 25-75 % lag per 50
LAGAddress 1-236 lag add 92
LAG STARTTimer 2-60 MIN lagstart 10
LAG STOP Timer 2-60 MIN lagstop 10
PRESTARTFAULT Timer 0-30 MIN preflt 5
STANDBYChiller Option DISABLE/ENABLE stndopt DISABLE
STANDBYPercent Capacity 25-75 % stnd per 50
STANDBYAddress 1-236 stnd add 93
NOTE: The Lead/Lag Configuration table is available on PSIO Software Version 09 and higher.
23