Physical Data — Tables 12-17 and Fig. 47-51 pro-

vide additional information regarding compressor fits and clearances, physical and electrical data, and wiring sche-

matics for operator convenience during troubleshooting.

Table 12 — Heat Exchanger Data

COOLER

VESSEL HEAT
EXCHANGER
CODE
NUMBER
OF TUBES
RIGGING WEIGHTS VESSEL CHARGE
Dry Wt. Refrigerant Volume
of Water
Design I Design II DesignI Design II
HCFC-22 HCFC-22 HFC-134a
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Gal L
COOLER
40 201 5000 2275 5340 2422 1020 463 750 341 550 250 53 201
41 227 5150 2350 5485 2488 1090 494 800 363 600 272 58 220
42 257 5325 2425 5655 2565 1150 522 900 408 650 295 64 242
43 290 5500 2500 5845 2651 1200 544 1000 454 700 318 71 269
50 314 6625 3000 7020 3184 1450 658 1150 522 750 341 79 299
51 355 6850 3100 7255 3291 1500 680 1250 568 850 386 87 329
52 400 7100 3225 7510 3406 1580 717 1400 636 950 431 96 363
53 445 7375 3350 7770 3524 1650 748 1500 681 1000 454 104 394
55 201 8510 3860 1410 640 1060 481 104 395
56 227 8845 4012 1710 776 1160 527 115 438
57 257 9205 4175 2010 913 1260 572 128 486
58 290 9575 4343 2210 1003 1410 640 140 531

CONDENSER

VESSEL HEAT
EXCHANGER
CODE
NUMBER
OF TUBES
RIGGING WEIGHTS VESSEL CHARGE
Dry Wt. Refrigerant Volume
of Water
Design I DesignII DesignI Design II
Lb Kg Lb Kg Lb Kg Lb Kg Gal L
CONDENSER
40 218 5050 2100 4855 2202 400 181 350 159 56 212
41 246 5200 2350 5010 2272 400 181 350 159 62 235
42 279 5375 2450 5180 2350 400 181 350 159 68 257
43 315 5575 2525 5370 2436 400 181 350 159 75 284
50 347 7050 3200 6750 3062 400 181 350 159 84 318
51 387 7275 3300 6960 3157 400 181 350 159 92 348
52 432 7500 3400 7200 3266 400 181 350 159 101 382
53 484 7775 3525 7475 3391 400 181 350 159 110 416
55 218 8345 3785 490 222 112 423
56 246 8635 3917 490 222 123 466
57 279 8980 4073 490 222 135 513
58 315 9370 4250 490 222 149 565
NOTES:
1. Design I chillers are equipped with a float box, and chiller weight is based on a 150 psi (1034 kPa)
waterbox with 2 pass arrangement.
2. DesignII chillers are equipped with a linear float, and chiller weight is based on a 300 psi (2068 kPa)
waterbox with 1 pass arrangement.
3. Total refrigerant charge is equal to the cooler charge added to the condenser charge.

Table 13 —Additional Data for Marine Waterboxes*

HEATEXCHANGER
FRAME, PASS
ENGLISH SI
Rigging Wt
(lb) WaterVolume
(gal) Rigging Wt
(kg) WaterVolume
(L)
Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser
FRAME 4, 2 PASS 1115 660 69 51 506 300 261 193
FRAME 4,1&3PASS 2030 1160 138 101 922 527 524 384
FRAME 5, 2 PASS 1220 935 88 64 554 424 331 243
FRAME 5,1&3PASS 2240 1705 175 128 1017 774 663 486
*Add to heat exchanger weights and volumes for total weight or volume.
85