Table 2 — LID Screens (cont)
EXAMPLE 8 — SERVICE2 DISPLAYSCREEN
Toaccess this display from the LID default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE2.
6.Press SELECT .
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULTVALUE
OPTIONS BOARD 1
20 mAPOWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mAPower Source 0,1 res 20ma 0
DEMAND 20 mAPower Source 0,1 dem 20 ma 0
SPAREALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp= Alert Threshold
CHWS TempEnable 0-2 chws en 0
CHWS TempAlert –40-245(–40-118) DEG F (DEG C) chws al 245 (118)
CHWR TempEnable 0-2 chwr en 0
CHWR TempAlert –40-245(–40-118) DEGF (DEG C) chwr al 245 (118)
Reset TempEnable 0-2 rres en 0
Reset TempAlert –40-245 (–40-118) DEG F (DEG C) rres al 245 (118)
Spare Temp1 Enable 0-2 spr1 en 0
Spare Temp1 Alert –40-245(–40-118) DEG F (DEG C) spr1 al 245 (118)
Spare Temp2 Enable 0-2 spr2 en 0
Spare Temp2 Alert –40-245(–40-118) DEG F (DEG C) spr2 al 245 (118)
Spare Temp3 Enable 0-2 spr3 en 0
Spare Temp3 Alert –40-245(–40-118) DEG F (DEG C) spr3 al 245 (118)
OPTIONS BOARD 2
20 mAPOWER CONFIGURATION
External = 0, Internal = 1
SPARE1 20 mA Power Source 0,1 sp1 20 ma 0
SPARE2 20 mA Power Source 0,1 sp2 20 ma 0
SPAREALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp= Alert Threshold
Spare Temp4 Enable 0-2 spr4 en 0
Spare Temp4 Alert –40-245(–40-118) DEG F (DEG C) spr4 al 245 (118)
Spare Temp5 Enable 0-2 spr5 en 0
Spare Temp5 Alert –40-245(–40-118) DEG F (DEG C) spr5 al 245 (118)
Spare Temp6 Enable 0-2 spr6 en 0
Spare Temp6 Alert –40-245(–40-118) DEG F (DEG C) spr6 al 245 (118)
Spare Temp7 Enable 0-2 spr7 en 0
Spare Temp7 Alert –40-245(–40-118) DEG F (DEG C) spr7 al 245 (118)
Spare Temp8 Enable 0-2 spr8 en 0
Spare Temp8 Alert –40-245(–0-118) DEG F (DEG C) spr8 al 245(118)
Spare Temp9 Enable 0-2 spr9 en 0
Spare Temp9 Alert –40-245(–40-118) DEG F (DEG C) spr9 al 245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘TempAlert’’ threshold for each point listed. If the
‘‘Enable’’is set to 1, a value above the ‘‘TempAlert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp
Alert’’threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.
EXAMPLE 9 — SERVICE3 DISPLAYSCREEN
Toaccess this display from the LID default screen:
1. Press MENU .
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE3.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Proportional Inc Band 2-10 gv inc 6.5
Proportional Dec Band 2-10 gv de 6.0
Proportional ECW Gain 1-3 gv ecw 2.0
Guide VaneTravel Limit 30-100 % gv lim 50
25