Table 9 Ð LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

 

 

 

 

 

 

 

 

 

Compressor is running with more than

UNAUTHORIZED

UNIT SHOULD BE

CA

 

 

 

P Emergency: Compressor

10% RLA and control is trying to shut it

 

 

 

down. Throw power off to compressor if

OPERATION

STOPPED

running without control authorization.

unable to stop. Determine cause before

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

repowering.

POTENTIAL FREEZE-UP

EVAP PRESS/TEMP

ERT Emergency: Freeze-up

Determine cause. If pumping refrigerant

out of chiller, stop operation and go over

TOO LOW

prevention.

 

pumpout procedures.

 

 

 

 

 

 

 

 

 

FAILURE TO STOP

DISCONNECT POWER

RUN

 

 

 

AUX Emergency: DISCON-

Starter and run and start contacts are

 

 

 

energized while control tried to shut

NECT POWER.

 

 

down. Disconnect power to starter.

 

 

 

 

 

 

 

 

 

LOSS OF

WITH STARTER

Loss of Communication with Starter:

Check wiring from PSIO to SMM. Check

COMMUNCIATION

Check chiller.

SMM module troubleshooting procedures.

 

STARTER CONTACT

ABNORMAL 1CR OR

1CR

 

 

AUX Starter Contact Fault:

Starter run and start contacts energized

FAULT

RUN AUX

Check 1CR/1M aux. contacts.

while chiller was off. Disconnect power.

 

 

 

 

 

 

 

 

 

The condenser pressure transducer is

 

 

CRT [VALUE] exceeded limit of

reading a pressure that could freeze the

POTENTIAL FREEZE UP

COND PRESS/TEMP

water in the condenser tubes. Check for

[LIMIT]* Emergency: Freeze-up

condenser refrigerant leaks, bad trans-

TOO LOW

 

prevention.

ducers, or transferred refrigerant. Place

 

 

 

 

 

 

 

 

 

 

 

the unit in Pumpdown mode to eliminate

 

 

 

 

 

 

 

 

 

ALARM if vessel is evacuated.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND

PRIMARY MESSAGE

SECONDARY MESSAGE

PROBABLE CAUSE/REMEDY

RUNNING Ð RESET ACTIVE

4-20MA SIGNAL

 

RUNNING Ð RESET ACTIVE

REMOTE SENSOR CONTROL

Reset program active based upon Con®g table setup.

RUNNING Ð RESET ACTIVE

CHW TEMP DIFFERENCE

 

RUNNING Ð TEMP CONTROL

LEAVING CHILLED WATER

Default method of temperature control.

RUNNING Ð TEMP CONTROL

ENTERING CHILLED WATER

ECW control activated on Con®g table.

RUNNING Ð TEMP CONTROL

TEMPERATURE RAMP LOADING

Ramp loading in effect. Use Service1 table to modify.

RUNNING Ð DEMAND LIMITED

BY DEMAND RAMP LOADING

Ramp loading in effect. Use Service1 table to modify.

RUNNING Ð DEMAND LIMITED

BY LOCAL DEMAND SETPOINT

Demand limit setpoint is , actual demand.

RUNNING Ð DEMAND LIMITED

BY 4-20MA SIGNAL

 

RUNNING Ð DEMAND LIMITED

BY CCN SIGNAL

Demand limit is active based on Con®g table setup.

RUNNING Ð DEMAND LIMITED

BY LOADSHED/REDLINE

 

RUNNING Ð TEMP CONTROL

HOT GAS BYPASS

Hot Gas Bypass is energized. See surge prevention

in the control section.

 

 

RUNNING Ð DEMAND LIMITED

BY LOCAL SIGNAL

Active demand limit manually overridden or Status01

table.

 

 

RUNNING Ð TEMP CONTROL

ICE BUILD MODE

Chiller is running under Ice Build temperature control.

 

 

 

NOTE: See Legend on page 68.

 

 

71

Page 71
Image 71
Carrier 19XL specifications Compressor Jumpstart and Refrigerant Protection, Normal RUN with RESET, TEMPERATURE, or Demand

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.