Table 9 Ð LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

RUN CAPACITY

HIGH CONDENSER PRESSURE

CRP [VALUE]* exceeded limit of

 

LIMITED

[LIMIT]*. Condenser pressure override.

 

 

 

RUN CAPACITY

HIGH MOTOR TEMPERATURE

MTRW [VALUE]* exceeded limit of

 

LIMITED

[LIMIT]*. Motor temperature override.

 

 

See Capacity Overrides, Table 4.

RUN CAPACITY

 

ERT [VALUE]* exceeded limit of

LOW EVAP REFRIG TEMP

Correct operating condition, modify

LIMITED

[LIMIT]*. Check refrigerant charge level.

 

setpoint, or release override.

RUN CAPACITY

HIGH COMPRESSOR LIFT

Surge Prevention Override; lift too high

 

LIMITED

for compressor.

 

 

 

RUN CAPACITY

MANUAL GUIDE VANE TARGET

GV

 

TRG Run Capacity Limited:

 

LIMITED

Manual guide vane target.

 

 

 

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point prede®ned or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.

J. OUT-OF-RANGE SENSOR FAILURES

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

SENSOR FAULT

LEAVING CHW TEMPERATURE

Sensor Fault: Check leaving CHW

 

sensor.

 

 

 

 

SENSOR FAULT

ENTERING CHW TEMPERATURE

Sensor Fault: Check entering CHW

 

sensor.

 

 

 

 

SENSOR FAULT

CONDENSER PRESSURE

Sensor Fault: Check condenser

 

pressure transducer.

 

 

 

 

SENSOR FAULT

EVAPORATOR PRESSURE

Sensor Fault: Check evaporator

 

pressure transducer.

 

 

 

See sensor test procedure and

SENSOR FAULT

 

Sensor Fault: Check bearing

BEARING TEMPERATURE

check sensors for proper operation

temperature sensor.

 

 

and wiring.

SENSOR FAULT

MOTOR WINDING TEMP

Sensor Fault: Check motor temperature

 

sensor.

 

 

 

 

SENSOR FAULT

DISCHARGE TEMPERATURE

Sensor Fault: Check discharge

 

temperature sensor.

 

 

 

 

SENSOR FAULT

OIL SUMP TEMPERATURE

Sensor Fault: Check oil sump

 

temperature sensor.

 

 

 

 

SENSOR FAULT

OIL PRESSURE TRANSDUCER

Sensor Fault: Check oil pressure

 

transducer.

 

 

 

 

NOTE: See Legend on page 68.

72

Page 72
Image 72
Carrier 19XL specifications Normal RUN Overrides Active Alerts, OUT-OF-RANGE Sensor Failures, Limited

19XL specifications

The Carrier 19XL is a highly regarded commercial heating and cooling solution, designed to provide optimum performance and energy efficiency in various applications. This rooftop unit is engineered to meet the diverse needs of businesses, making it an ideal choice for those requiring reliable climate control in their facilities.

One of the standout features of the Carrier 19XL is its advanced cooling and heating capabilities. The unit utilizes a high-efficiency scroll compressor that ensures a quieter operation and improved reliability. The system can operate across a wide range of temperatures, making it versatile for various climates. Additionally, it offers both cooling and heating options, allowing for year-round comfort.

Energy efficiency is a focal point of the 19XL design. With an impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF), this unit not only helps reduce energy costs but also supports environmental sustainability initiatives. The unit is equipped with environmentally friendly refrigerants, further contributing to lower greenhouse gas emissions.

The Carrier 19XL features a user-friendly control system, allowing for easy monitoring and management of the unit's performance. This control system is designed to maximize energy savings, offering features such as demand control ventilation and integrated economizers that facilitate the use of outdoor air for cooling, reducing reliance on mechanical systems when conditions allow.

Construction-wise, the Carrier 19XL is built to withstand tough environmental conditions. Its robust cabinet is made from galvanized steel, providing durability and protection against the elements. The design also includes insulation to minimize noise levels, creating a more comfortable indoor environment.

Maintenance is a key consideration in the design of the 19XL. The unit features accessible service ports and a simplified access panel, allowing technicians to perform routine maintenance with ease. This proactive design helps ensure the longevity of the system and minimizes downtime, keeping operations running smoothly.

In summary, the Carrier 19XL is an exceptional choice for commercial heating and cooling needs. With its energy-efficient features, advanced technology, and durable construction, it stands out as a reliable solution for businesses looking for sustainable climate control options.