Carrier 48PG20-28 specifications LEGEND AND NOTES FOR TABLES 4A AND 4B, Outdoor-AirHood Details

Models: 48PG20-28

1 64
Download 64 pages 4.71 Kb
Page 15
Image 15
LEGEND AND NOTES FOR TABLES 4A AND 4B

LEGEND AND NOTES FOR TABLES 4A AND 4B

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and com- bination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percent voltage imbalance.

%Voltage Imbalance

=100 x max voltage deviation from average voltage average voltage

 

TOP HOOD

 

SECTION

SEAL

HOOD

STRIP

SIDE

LOCATION

 

BOTTOM

 

HOOD

 

SECTION

 

FILTERFig. 18 — Outdoor-Air Hood Details

GUIDE

FILTER

RETAINER

FILTER

MANUAL

DAMPER

(IF EQUIPPED)

NOTE: Units with manual damper only use one filter.

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage=

3

= 1371 3

= 457

Determine maximum deviation from average voltage. (AB) 457 - 452 = 5 v

(BC) 464 - 457 = 7 v (AC) 457 - 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x 457

=1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact the local electric utility company immediately.

3.The convenience outlet full load amps (FLA) are 5, 3, and 3 for 208/230, 460, 575-V units, respectively.

ADD

SEAL

STRIP

ADD

SEAL

STRIP INNER

FILTER

TRACK

ADD

SEAL

STRIP

ADD

SEAL

STRIP

FILTER

GUIDE

HOOD

SIDE

UNIT

BACK

PANEL

Fig. 18 — Outdoor-Air Hood Details

15

Page 15
Image 15
Carrier 48PG20-28 specifications LEGEND AND NOTES FOR TABLES 4A AND 4B, Outdoor-AirHood Details