Table 25 — Evaporator Fan Motor Specifications (cont)

48PG

DRIVE

ORIENTATION

MOTOR P/N

NOMINAL HP

VOLTAGE

MAX WATTS

EFFICIENCY %

MAX BHP

MAX BkW

MAX AMPS

 

 

 

HD60FK651

3.7

208

3698

85.8

4.25

3.17

10.6

 

Low

Vertical

HD60FK651

3.7

230

3698

85.8

4.25

3.17

9.6

 

HD60FK651

3.7

460

3698

85.8

4.25

3.17

4.8

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

Mid-Low

Vertical

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD62FK652

7.5

208

7267

88.5

8.63

6.43

24.2

 

Mid-High

Vertical

HD62FK652

7.5

230

7267

88.5

8.63

6.43

22

 

HD62FK652

7.5

460

7267

88.5

8.63

6.43

11

 

 

 

 

 

 

HD62FK576

7.5

575

7267

88.5

8.63

6.43

9

 

 

 

HD64FK651

10

208

9582

89.5

11.5

8.58

30.8

 

High

Vertical

HD64FK651

10

230

9582

89.5

11.5

8.58

28

 

HD64FK651

10

460

9582

89.5

11.5

8.58

14

 

 

 

24

 

 

HD64FK575

10

575

9582

89.5

11.5

8.58

11

 

 

N/A

N/A

208

N/A

N/A

N/A

N/A

N/A

 

 

 

 

Low

Horizontal

N/A

N/A

230

N/A

N/A

N/A

N/A

N/A

 

N/A

N/A

460

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

N/A

N/A

575

N/A

N/A

N/A

N/A

N/A

 

 

 

HD60FK651

3.7

208

3698

85.8

4.25

3.17

10.6

 

Mid-Low

Horizontal

HD60FK651

3.7

230

3698

85.8

4.25

3.17

9.6

 

HD60FK651

3.7

460

3698

85.8

4.25

3.17

4.8

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

Mid-High

Horizontal

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD62FK652

7.5

208

7267

88.5

8.63

6.43

24.2

 

High

Horizontal

HD62FK652

7.5

230

7267

88.5

8.63

6.43

22

 

HD62FK652

7.5

460

7267

88.5

8.63

6.43

11

 

 

 

 

 

 

HD62FK576

7.5

575

7267

88.5

8.63

6.43

9

 

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

Low

Vertical

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

Mid-Low

Vertical

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD62FK652

7.5

208

7267

88.5

8.63

6.43

24.2

 

Mid-High

Vertical

HD62FK652

7.5

230

7267

88.5

8.63

6.43

22

 

HD62FK652

7.5

460

7267

88.5

8.63

6.43

11

 

 

 

 

 

 

HD62FK576

7.5

575

7267

88.5

8.63

6.43

9

 

 

 

HD64FK651

10

208

9582

89.5

11.5

8.58

30.8

 

High

Vertical

HD64FK651

10

230

9582

89.5

11.5

8.58

28

 

HD64FK651

10

460

9582

89.5

11.5

8.58

14

 

 

 

28

 

 

HD64FK575

10

575

9582

89.5

11.5

8.58

11

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

 

 

 

Low

Horizontal

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD60FK653

5

208

4900

87.5

5.75

4.29

16.7

 

Mid-Low

Horizontal

HD60FK653

5

230

4900

87.5

5.75

4.29

15.2

 

HD60FK653

5

460

4900

87.5

5.75

4.29

7.6

 

 

 

 

 

 

HD60FK575

5

575

4900

87.5

5.75

4.29

6.1

 

 

 

HD62FK652

7.5

208

7267

88.5

8.63

6.43

24.2

 

Mid-High

Horizontal

HD62FK652

7.5

230

7267

88.5

8.63

6.43

22

 

HD62FK652

7.5

460

7267

88.5

8.63

6.43

11

 

 

 

 

 

 

HD62FK576

7.5

575

7267

88.5

8.63

6.43

9

 

 

 

HD64FK651

10

208

9582

89.5

11.5

8.58

30.8

 

High

Horizontal

HD64FK651

10

230

9582

89.5

11.5

8.58

28

 

HD64FK651

10

460

9582

89.5

11.5

8.58

14

 

 

 

 

 

 

HD64FK575

10

575

9582

89.5

11.5

8.58

11

NOTES:

1.Extensive motor and electrical testing ensures that the motors can be uti- lized with confidence up to the maximum applied bhp, watts, and amps. Using the fan motor up to the maximum ratings shown will not result in nui- sance tripping or premature motor failure. Unit warranty will not be affected.

2.All indoor-fan motors 5 hp and larger meet the minimum efficiency require- ments as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997.

38

Page 38
Image 38
Carrier 48PG20-28 specifications Evaporator Fan Motor Specifications