Table 9 — Fan Performance — 48PGE24 — Vertical Supply/Return Units

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5,500

 

652

 

1.90

 

719

 

2.19

 

779

 

2.47

 

833

 

2.74

A

884

 

3.01

6,000

 

699

 

2.32

A

763

 

2.63

A

819

 

2.93

A

872

 

3.22

921

 

3.50

 

 

 

 

 

 

 

6,500

A

746

 

2.79

807

 

3.12

861

 

3.44

 

911

 

3.75

 

958

 

4.05

 

 

 

 

 

 

 

 

 

7,000

794

 

3.33

 

851

 

3.68

 

904

 

4.02

 

952

 

4.34

B

998

 

4.66

 

 

 

 

 

 

 

 

 

7,500

 

842

 

3.93

 

897

 

4.30

 

947

 

4.65

B

994

 

5.00

 

1038

 

5.33

8,000

 

891

 

4.59

 

943

 

4.98

B

991

 

5.35

 

1036

 

5.71

 

1079

 

6.07

8,500

 

940

 

5.32

B

990

 

5.72

 

1036

 

6.11

 

1080

 

6.49

C

1121

 

6.87

9,000

C

990

 

6.12

 

1037

 

6.54

C

1082

 

6.95

C

1124

 

7.35

 

1163

 

7.73

9,500

1039

 

7.00

C

1085

 

7.43

 

1128

 

7.85

 

1168

 

8.27

D

1207

 

8.67

 

 

 

 

 

 

 

 

10,000

 

1089

 

7.95

 

1133

 

8.40

D

1174

 

8.83

D

1213

 

9.26

1251

 

9.69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5,500

A

933

 

3.27

 

979

 

3.54

 

1023

 

3.80

 

1066

 

4.06

 

1108

 

4.33

6,000

 

967

 

3.79

B

1011

 

4.07

B

1054

 

4.35

B

1095

 

4.62

B

1135

 

4.90

6,500

B

1003

 

4.35

 

1046

 

4.65

 

1087

 

4.94

 

1127

 

5.24

 

1165

 

5.53

7,000

1041

 

4.98

 

1082

 

5.29

 

1122

 

5.60

C

1160

 

5.91

 

1197

 

6.22

7,500

 

1079

 

5.67

C

1119

 

5.99

C

1158

 

6.32

 

1195

 

6.64

D

1231

 

6.96

8,000

C

1119

 

6.42

1158

 

6.76

 

1195

 

7.10

D

1231

 

7.44

 

1267

 

7.78

8,500

1160

 

7.23

 

1198

 

7.59

D

1234

 

7.95

 

1269

 

8.30

 

1303

 

8.65

 

 

 

 

 

 

 

 

 

9,000

 

1202

 

8.12

D

1238

 

8.49

 

1273

 

8.87

 

1308

 

9.23

 

1341

 

9.60

9,500

D

1244

 

9.07

 

1279

 

9.46

 

1314

 

9.85

 

1347

 

10.24

 

1379

 

10.62

10,000

 

1287

 

10.10

 

1321

 

10.51

 

1355

 

10.91

 

1387

 

11.31

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Boldface indicates field-supplied motor/drive required.

NOTES:

1.Motor drive ranges:

(A)Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)

(B)Mid-Low Range: 949-1206 rpm, 5.75 bhp

(C)Mid-High Range: 941-1176 rpm, 8.63 bhp

(D)High Range: 1014-1297 rpm, 11.50 bhp

All other rpms require field-supplied motor or drive.

2. See page 36 for general fan performance notes.