Table 20 — Fan Performance — 48PGD28 — Horizontal Supply and Return Units

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

6,500

 

E

786

 

2.50

E

819

 

2.70

E

857

 

2.96

 

899

 

3.25

F

943

 

3.59

7,000

 

842

 

3.09

871

 

3.30

 

905

 

3.55

F

943

 

3.85

983

 

4.19

 

 

 

 

 

 

 

 

 

 

7,500

 

F

898

 

3.77

F

925

 

3.99

F

955

 

4.24

 

989

 

4.54

 

1026

 

4.88

8,000

 

955

 

4.55

979

 

4.77

 

1007

 

5.03

 

1037

 

5.33

G

1070

 

5.67

 

 

 

 

 

 

 

 

 

 

8,500

 

 

1012

 

5.42

 

1034

 

5.65

 

1059

 

5.92

G

1087

 

6.22

1117

 

6.56

 

 

 

 

 

 

 

 

 

 

9,000

 

G

1069

 

6.41

G

1090

 

6.65

G

1113

 

6.92

 

1138

 

7.23

 

1165

 

7.57

9,500

 

 

1127

 

7.51

 

1146

 

7.76

 

1167

 

8.04

 

1190

 

8.35

H

1215

 

8.69

10,000

 

H

1184

 

8.74

H

1202

 

8.99

H

1221

 

9.28

H

1243

 

9.59

1266

 

9.93

 

 

 

 

 

 

 

10,500

 

1242

 

10.09

1258

 

10.35

1276

 

10.64

 

1296

 

10.96

 

1318

 

11.31

 

 

 

 

 

 

 

 

 

 

 

11,000

 

 

1299

 

11.58

 

1315

 

11.85

 

1332

 

12.15

 

1350

 

12.47

 

1370

 

12.82

11,500

 

 

1357

 

13.20

 

1372

 

13.48

 

1388

 

13.79

 

 

 

 

12,000

 

 

 

 

 

 

 

 

 

 

 

12,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

6,500

 

F

988

 

3.97

 

1035

 

4.39

 

1082

 

4.87

G

1129

 

5.39

 

1177

 

5.95

7,000

 

 

1024

 

4.57

G

1066

 

4.98

G

1109

 

5.43

1153

 

5.93

 

1197

 

6.48

7,500

 

G

1063

 

5.25

1102

 

5.66

1141

 

6.11

 

1181

 

6.59

H

1221

 

7.11

 

 

 

 

 

 

 

 

 

8,000

 

 

1105

 

6.04

 

1140

 

6.45

 

1176

 

6.89

H

1213

 

7.36

 

1250

 

7.87

8,500

 

 

1149

 

6.94

 

1181

 

7.34

 

1215

 

7.78

1249

 

8.25

 

1283

 

8.74

9,000

 

 

1194

 

7.94

H

1225

 

8.35

H

1256

 

8.79

 

1287

 

9.25

 

1319

 

9.74

9,500

 

H

1242

 

9.07

 

1270

 

9.47

 

1298

 

9.91

 

1328

 

10.37

 

1358

 

10.87

10,000

 

 

1290

 

10.31

 

1316

 

10.72

 

1343

 

11.16

 

1370

 

11.62

 

1399

 

12.11

10,500

 

 

1340

 

11.69

 

1364

 

12.10

 

1389

 

12.54

 

 

 

 

11,000

 

 

1391

 

13.20

 

 

 

 

 

 

 

 

11,500

 

 

 

 

 

 

 

 

 

 

 

12,000

 

 

 

 

 

 

 

 

 

 

 

12,500

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bhp —

Brake Horsepower Input to Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boldface indicates field-supplied motor/drive required.

NOTES:

1.Motor drive ranges:

(E)Low Range: 687-873 rpm, 5.75 bhp

(F)Mid-Low Range: 805-1007 rpm, 5.75 bhp

(G)Mid-High Range: 941-1176 rpm, 8.63 bhp

(H)High Range: 1014-1297 rpm, 11.50 bhp

All other rpms require field-supplied motor or drive.

2. See page 36 for general fan performance notes.

34

Page 34
Image 34
Carrier 48PG20-28 specifications Fan Performance 48PGD28 Horizontal Supply and Return Units, 1328 10.37 1358 10.87 10,000