Table 34 — Gas Heating Service Analysis

PROBLEM

CAUSE

REMEDY

Burners Will Not Ignite.

Misaligned spark electrodes.

Check flame ignition and sensor electrode positioning.

 

 

Adjust as needed.

 

No gas at main burners.

Check gas line for air; purge as necessary. After purging gas

 

 

line of air, allow gas to dissipate for at least 5 minutes before

 

 

attempting to relight unit.

 

 

Check gas valve.

 

Water in gas line.

Drain water and install drip leg to trap water.

 

No power to furnace.

Check power supply, fuses, wiring, and circuit breaker.

 

No 24 v power supply to control circuit.

Check transformer. Transformers with internal overcurrent pro-

 

 

tection require a cool-down period before resetting. Check 24-v

 

 

circuit breaker; reset if necessary.

 

Miswired or loose connections.

Check all wiring and wire nut connections.

 

Burned-out heat anticipator in thermostat.

Replace thermostat.

 

Broken thermostat wires.

Run continuity check. Replace wires if necessary.

Inadequate Heating.

Dirty air filter.

Clean or replace filter as necessary.

 

Gas input to unit too low.

Check gas pressure at manifold. Clock gas meter for input.

 

 

If too low, increase manifold pressure or replace with correct

 

 

orifices.

 

Unit undersized for application.

Replace with proper unit or add additional unit.

 

Restricted airflow.

Clean filter, replace filter, or remove any restrictions.

 

Blower speed too low.

Install alternate motor, if applicable, or adjust pulley to increase

 

 

fan speed.

 

Limit switch cycles main burners.

Check rotation of blower, thermostat heat anticipator settings,

 

 

and temperature rise of unit. Adjust as needed.

 

Too much outdoor air.

Adjust minimum position.

 

 

Check economizer operation.

Poor Flame Characteristics.

Incomplete combustion (lack of combustion air)

Check all screws around flue outlets and burner compartment.

 

results in:

Tighten as necessary.

 

Aldehyde odors, CO, sooting flame, or floating

Cracked heat exchanger. Replace heat exchanger.

 

flame.

 

 

Overfired unit — reduce input, change orifices, or adjust gas

 

 

 

 

line or manifold pressure.

 

 

Check vent for restriction. Clean as necessary.

 

 

Check orifice to burner alignment.

Burners Will Not Turn Off.

Unit is locked into Heating mode for a one minute

Wait until mandatory one minute time period has elapsed or

 

minimum.

power to unit.

58

Page 58
Image 58
Carrier 48PG20-28 specifications Gas Heating Service Analysis, Burners Will Not Ignite