Condenser Fans and Motors — Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section (page 49) as required.

Return-Air Filters — Check that correct filters are in- stalled in filter tracks (see Table 1). Do not operate unit without return-air filters.

NOTE: For units with 4-in. filter option, units are shipped with standard 2-in. filters. To install 4-in. filters, the filter spacers must be removed.

Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit.

Gas Heat — Verify gas pressures before turning on heat as follows:

1.Turn off field-supplied manual gas stop, located external to unit.

2.Connect pressure gage to supply gas tap, located on field- supplied manual shutoff valve (see Fig. 14).

3.Connect pressure gage to manifold pressure tap.

4.Turn on field-supplied manual gas stop. Temporarily install the jumper wire between “R” and “W1” on TB2. Set thermostat to HEAT and raise set point until heat comes on.

5.After the unit has run for several minutes, verify the sup- ply gas pressure is between 5.5 in. wg to 13.0 in. wg, and the manifold pressure is 2.95 in. wg on horizontal dis- charge applications and 3.00 on vertical discharge appli- cations. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section.

NOTE: Supply gas pressure must not exceed 13.0 in. wg.

6.Set thermostat to OFF.

7.Remove jumper wire if the unit will be operating under thermostat mode.

8.Return thermostat to desired set point.

Table 5 — Fan Performance — 48PGD20 Vertical Supply/Return Units

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

0.2

 

0.4

 

 

0.6

 

 

0.8

 

 

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5000

 

590

 

1.47

 

663

 

1.74

 

727

 

2.01

 

786

 

2.26

 

840

 

2.52

5500

 

633

 

1.82

 

703

 

2.11

 

764

 

2.40

 

820

 

2.67

A

872

 

2.94

6000

 

677

 

2.21

 

744

 

2.53

A

803

 

2.84

A

857

 

3.13

 

907

 

3.42

6500

 

722

 

2.67

A

786

 

3.01

 

842

 

3.33

 

894

 

3.64

 

942

 

3.95

7000

A

767

 

3.17

 

828

 

3.53

 

883

 

3.88

 

933

 

4.21

B

979

 

4.53

7500

 

813

 

3.74

 

871

 

4.12

 

924

 

4.48

B

972

 

4.83

1017

 

5.18

 

 

 

 

 

 

 

 

 

8000

 

859

 

4.36

 

915

 

4.77

B

966

 

5.15

1012

 

5.52

 

1056

 

5.88

 

 

 

 

 

 

 

 

 

8500

 

906

 

5.05

B

959

 

5.47

C

1008

 

5.87

C

1053

 

6.26

C

1096

 

6.64

9000

C

952

 

5.81

C

1004

 

6.25

1051

 

6.67

1095

 

7.07

 

1136

 

7.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

1.2

 

1.4

 

 

1.6

 

 

1.8

 

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

5000

 

891

 

2.77

 

940

 

3.02

 

987

 

3.27

 

1032

 

3.52

 

1076

 

3.77

5500

A

921

 

3.21

 

968

 

3.48

 

1014

 

3.74

B

1057

 

4.01

B

1099

 

4.27

6000

 

954

 

3.70

B

999

 

3.99

B

1042

 

4.27

1084

 

4.55

1125

 

4.83

 

 

 

 

 

 

 

 

6500

 

988

 

4.25

1032

 

4.55

 

1073

 

4.85

 

1114

 

5.14

 

1153

 

5.44

 

 

 

 

 

 

 

 

 

 

7000

B

1024

 

4.85

 

1066

 

5.17

 

1106

 

5.48

C

1145

 

5.79

 

1183

 

6.10

7500

 

1060

 

5.51

 

1101

 

5.84

C

1140

 

6.17

 

1178

 

6.50

D

1215

 

6.82

8000

 

1098

 

6.23

C

1138

 

6.58

1176

 

6.92

D

1213

 

7.26

1249

 

7.60

 

 

 

 

 

 

 

 

8500

C

1137

 

7.01

 

1175

 

7.38

D

1212

 

7.74

1248

 

8.09

 

1283

 

8.45

 

 

 

 

 

 

 

 

9000

1176

 

7.86

D

1214

 

8.24

1250

 

8.61

 

1285

 

8.99

 

1319

 

9.36

 

 

 

 

 

 

 

 

 

LEGEND

Bhp — Brake Horsepower Input to Fan

Boldface indicates field-supplied motor/drive required.

NOTES:

1.Motor drive ranges:

(A)Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)

(B)Mid-Low Range: 949-1206 rpm, 5.75 bhp

(C)Mid-High Range: 941-1176 rpm, 8.63 bhp

(D)High Range: 1014-1297 rpm, 11.50 bhp

All other rpms require field-supplied motor or drive.

2. See page 36 for general fan performance notes.

19

Page 19
Image 19
Carrier 48PG20-28 specifications Fan Performance 48PGD20 Vertical Supply/Return Units